Control panel mounting requirements. 1 –
control panel, 2 – vent holes to provide air
circulation (note: the holes may not cause
downgrading of required IP rating. They are
not
required
if
permitted
ambient
temperature around the control panel is not
exceeded.)
Disassembly of control panel:
To remove the control panel (1) from the
housing - insert flat elements (2) into
indicated slots to release housing catches
and remove the panel (1).
13.4
Mounting of working module
The executive module must be covered. The
cover must ensure a level of protection
relevant to the environment in which the
regulator will be used. Moreover, it must
prevent access to parts which are carrying
dangerous voltage, such as terminals. A
standard installation cabinet may be used as
the cover. In such case, the user has access
to the face plate of the executive module.
The cover may be composed from boiler
elements surrounding the whole module.
The module cover does not provide
resistance to dust and water. To protect it
from these factors, provide a suitable
additional cover.
The executive module is intended for
mounting on a standard DIN TS35 rail. The
rail must be installed tightly on a secure
surface. Before placing the module on the
rail (2), lift the pin (3) up. After placing the
module, press the pin (3) to its original
position. Make sure that the device is
installed securely and cannot be removed
from the rail without the use of tools.
For safety reasons, maintain a safe distance
between the active elements of the terminal
of the executive module and the conductive
(metal) elements of the cover (at least 10
mm).
The connection wires must be protected from
plucking it out and loosening, or covered in a
way that prevents the wires from tightening.
Содержание ecoMAX860P2-T
Страница 2: ...2...
Страница 6: ......
Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...
Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...