Metal-Fach ecoMAX860P2-T Скачать руководство пользователя страница 36

36 

 

  Fan speed 

Fan speed in SUPERVISION mode; too high value may cause the boiler 
to overheat or the flame to return to the feeder; too low value results in 
fuel over-filling. 

  Feed time 

Feed time in SUPERVISION mode; too high value may cause the boiler 
to  overheat  or  fuel  over-filling;  too  low  value  results  in  fuel  returning  to 
the container. 

  Interval time 

Feeder work cycle time in Supervision mode. 

SUPERVISION cycle time 

= feed time 

interval time 

 

  Fan time extension 

In  SUPERVISION mode,  after  a  fuel  dose is supplied and  the  feeder is 
off,  the  continues  to  work  for  the  extension  period  in  order  to  ignite  the 
fuel dose. This parameter should not be set too high as it may over heat 
the boiler. 

Min. Fan speed  

Minimal fan speed in % that can be selected by the user of the regulator. 
This  parameter  is  used  to  limit  the  access  to  the  complete  fan  speed 
range  in  the  user  menu.  It  is  not  used  in  the  fan  control  algorithm.  The 
parameter  should  be  set  relatively  low,  allowing  the  fan  to  spin  slowly 
and freely. 

Lack of fuel detection time 

 

Lack  of  fuel  detection  time  is  deduced  after  the  exhaust  temperature 
drops  below  the 

Lack  of  fuel  detection  threshold. 

After  this  time  is 

deduced, the regulator makes 3 attempts to ignite the burner, and when 
this fails, it displays the “ignition failed” alarm. 

Lack of fuel detection 
threshold 

Exhaust temperature increase 
time 

This  time  is  used  as  function  preventing  the  extinguishing  of  flame  in 
OPERATION  mode.  If  the  exhaust  temperature  does  not  exceed  the 

Lack of Fuel Detection threshold

 after such time, an ignition test will be 

made. 

Max. feeder temp.  

This parameter determines the maximum temperature at which the alarm 
for exceeding the maximum feeder temperature is displayed. When this 
temperature  is  exceeded,  the  feeder  is  engaged  for  a  predefined  time, 
with  a  several-minute  pause.  If  the  temperature  drops,  the  regulator 
resumes normal operation; if not, the feeder will be engaged for a longer 
period  in  order  to  remove  embers  from  the  feeding  pipe.  These  times 
may be edited in a special menu accessible only to the manufacturer of 
the boiler. 

15.2

 

 BOILER 

 

Boiler settings 

Grate

 

 

 

Max. ignition time 

When  this  time  is  exceeded  ant  the  exhaust  temperature  does  not  rise 
above the 

Lack of Fuel detection thr15°C, a failed ignition alarm 

will be displayed.  Note: during ignition in RUST mode, the fan works at 
the 

Ignition  fan  -  grate

  speed.  This  parameter  is  adjusted  via  the  user 

menu. 

 

Purge operation - supervision 

Fan  purge 

time  when  the  boiler  temperature  exceeds  the  boiler’s  set 

temperature  

 

Purge interval - supervision 

Fan purge interval time when the boiler temperature exceeds the boiler’s 
set temperature 

 

Lack of fuel detection time 

When  the  exhaust  temperature  in  OPERATION  mode  drops  below  the 

Lack  of  fuel  detection  threshold, 

lack  of  fuel  is  detected  and  the  fan  is 

stopped. 

 

Lack of fuel detection method 

Only  exhaust  -  lack  of  fuel  detection  occurs  via  the  indications  of  the 
exhaust  temperature  sensor.  This  method  allows  to  detect  the  lack  of 

fuel quickly. It can only be used when there is an exhaust sensor in the 
flue of the boiler.  
Water and exhaust - lack of fuel detection occurs both via the indications 
of the exhaust temperature sensor and the water temperature sensor in 
the  boiler.  To  detect  the  lack  of  fuel,  both  temperatures  need  to  drop, 
and  the  water  temperature  in  the  boiler  must  drop  below  the 

CH  pump 

activation temperature

 

Exhaust temperature - fan 
reduction 

In order to limit the chimney loss, the fan speed is reduced to the value 
of 

Fan  speed  30%   

This  happens  when  the  exhaust  temperature 

Содержание ecoMAX860P2-T

Страница 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Страница 2: ...2...

Страница 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Страница 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Страница 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Страница 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Страница 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Страница 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Страница 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Страница 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Страница 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Страница 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Страница 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Страница 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Страница 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Страница 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Страница 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Страница 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Страница 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Страница 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Страница 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Страница 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Страница 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Страница 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Страница 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Страница 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Страница 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Страница 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Страница 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Страница 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Страница 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Страница 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Страница 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Страница 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Страница 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Страница 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Страница 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Страница 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Страница 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: