SERVICE SETTINGS 

15.1

 

BURNER 

Burner settings 

Firing-up 

 

  Ignition test time 

Time  of  checking  whether  the  burner  is  ignited.  The  regulator  checks  if 
there  was  a  proper  rise  (increase)  of  exhaust  temperature.  After 
successfully  completing  the  check,  the  regulator  switches  to 
OPERATION mode. 

  Feed time 

Fuel dosage feed time at ignition. 

  End-ignition exhaust temp. 

Exhaust temperature above which the burner is considered to be ignited. 
Ignition  test  is  ignored.  Note:  setting  a  low  temperature  may  result  in 
switching to OPERATION mode without a sufficient flame in the furnace. 
Recommended value: 130-

150 °C. 

  Exhaust delta 

Rise  (increase)  of  exhaust  temperature  necessary  to  switch  to 
OPERATION mode. 

  Ignition fan 

Fan  %  at  ignition.  Note:  setting  a  high  value  will  prolong  the  ignition 
process and result in failed ignition attempt. 

  Ignition time 

Time  of  consecutive  ignition  attempts.  After  this  time,  the  regulator  will 
make another ignition attempt (max. 3 attempts). 

  Fan time extension 

Between each ignition attempt, the fan works without the heater. Thanks 
to this, before making another ignition attempt, the possible flame in the 
burner has a chance to increase the exhaust temperature and cause the 
switch  from  IGNITION  to  OPERATION  mode  without  the  need  for 
additional ignition attempts.  

  Heating-up time 

Igniter heating-up time before switching on the fan. 

This should not be 

set  too  high  to  prevent  damage  to  the  heater.

  After  such  time,  the 

heater continues to work until an increase in the exhaust temperature is 
detected. 

Operation 

 

  OPERATION mode cycle time 

Complete cycle time of fuel feeding in OPERATION mode. 

OPERATION 

cycle time = OPERATION feed time 

+ feeder standstill time 

  Feeder efficiency 

Efficiency of the fuel feeder in kg/h. Entered a measured amount of fuel 
in  constant  feed  (feeder  working  constantly).  The  parameter  does  not 
affect the work of the burner and is used for calculating the fuel level and 
current boiler output. 

  Fuel caloric value 

Fuel caloric value in Kwh/kg. This parameter is only used for information. 
The  parameter  does  not  affect  the  work  of  the  burner  and  is  used  for 
calculating the fuel level and current boiler output. 

  Container capacity 

Fuel container capacity used for calculating the fuel level.   Entering the 
correct  value  relieves  the  user  from  the need  to  calibrate  the  fuel level. 
The  regulator  uses  this  data  if  the  fuel  level  has  not  been  calibrated. 
After  calibrating  the  fuel  level  successfully,  the  regulator  does  not  use 
this parameter. 

  Feeder 

It is possible to conduct a feeder efficiency test and to set the duration of 
this  test.  Additionally,  fuel  weight  can  be  entered  here.  This  data 
facilitates the adjustment of fuel oriented parameters. 

Burning off 

BURNING OFF mode is not used when coal is the fuel of choice. 

  Burning off time 

Fan time in order to burn off remaining fuel.  

  Purge speed 

Fan speed during burning off in %.  

Supervision 

 

  Supervision time 

BURNING OFF mode and then into PAUSE mode. When the parameter 

Supervision  time  =  0

,  then  the  controller  skip  the  SUPERVISION  mode 

and  goes  directly  to  BURNING  OFF  mode.  When  the  parameter 

Supervision  time  =  255

then  the  controller  stays  in  SUPERVISION 

mode

 

until  the  boiler  temperature  drops  down  up  to  the  level,  by  which 

the controller returns to OPARATION mode. 

Содержание ecoMAX860P2-T

Страница 1: ...C SOLID FUEL FIRED BOILERS WITH INGITION GUTTER AND RETORT FEEDERS INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A B PANEL v06 XX XX v06 XX XX 11 2015 functions available in t...

Страница 2: ...2...

Страница 3: ...VERHEATING STB LIMITER OPEN 18 9 10 MAX EXHAUST TEMPERATURE EXCEEDED SENSOR DAMAGE DANGER 18 9 11 LACK OF COMMUNICATION 18 9 12 UNSUCCESSFUL ATTEMPT OF BUFFER LOADING 18 9 13 FAN OR FAN SPEED SENSOR F...

Страница 4: ...flame going back to the fuel feeder etc The regulator is intended for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boi...

Страница 5: ...to two parts for user and fitter Yet both parts contain important information significant for safety issues hence the user should read both parts of the manual We are not responsible for any damages c...

Страница 6: ......

Страница 7: ...REGULATOR INSTRUCTION MANUAL ecoMAX860P2 T...

Страница 8: ...Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decrease...

Страница 9: ...been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the time of HUW container filling increase of preset boiler temperature by mixer circuit i...

Страница 10: ...lted Boiler operation cannot be continued automatically service crew must intervene After removing causes of impossibility to fire up the boiler must be restarted 8 5 OPERATION The fan operates contin...

Страница 11: ...ime expires the regulator switches to EXTINGUISHING mode unless the boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulato...

Страница 12: ...ght time decrease and Service Settings CH and HUW settings The time settings of the circulation pump are analogous to the settings of night time decrease The pump will be off in the defined time perio...

Страница 13: ...e heating cycle temperature by a constant value when the preset room temperature is reached Analogously as specified in the previous point not recommended or automatically continuously correct the hea...

Страница 14: ...have good thermal insulation the heating curve can have lower value The regulator can increase or decrease the preset temperature calculated in accordance with the heating curve if it exceeds the tem...

Страница 15: ...selected and confirmed YES fuel level is set to 100 Note Fuel may be replenished at any time without a need to wait for complete empty fuel tank Replenish fuel always to the level corresponding to 100...

Страница 16: ...tom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in pie menu for a while To remove selected item...

Страница 17: ...er control is taken over by the emergency system and the boiler continues to operate Note operating in emergency mode is allowed only under user supervision and until the arrival of the service team t...

Страница 18: ...igital communication link In case a cable of this link will be damaged an alarm will occur on the screen with the information Attention No communication The controller doesn t stop to operate and work...

Страница 19: ...19 CONTROLLER INSTALLATION AND SERVICE SETTINGS MANUAL ecoMAX860P2 T...

Страница 20: ...rature set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid...

Страница 21: ...ctivation temperature 55 C Menu service settings CH and HUW settings CH pump boiler pump YES Menu service settings CH and HUW settings Mixer 1 control CH activated Menu service settings Mixer 1 contro...

Страница 22: ...ice settings buffer settings Buffer load activation temperature 50 Menu service settings buffer settings Buffer load deactivation temperature 75 Menu service settings buffer settings Mixer 1 control C...

Страница 23: ...vibrations greater than those typical of normal road transport 13 REGULATOR INSTALLATION 13 1 Environmental conditions Due to the risk of fire is prohibited to use the controller in explosive gas and...

Страница 24: ...In such case the user has access to the face plate of the executive module The cover may be composed from boiler elements surrounding the whole module The module cover does not provide resistance to...

Страница 25: ...in accordance with this drawing the device has protection rate IP 20 from the front side of the executive module enclosure specified on the rating plate From the side of the terminals the casing has p...

Страница 26: ...ation with low voltage devices below 12 V Connecting mains supply 230V to terminals 22 49 and to transmission connectors RS485 will damage the regulator and creates risk of an electric shock Tips of t...

Страница 27: ...1 temperature sensor M2 CT4 regulated circuit mixer 2 temperature sensor WS CT6 P weather sensor FT CT2S exhaust temperature sensor BP control panel B additional heating circuits control module lambd...

Страница 28: ...RM4 mixer 4 room thermostat FS fuel level sensor used with the BU feeder H2 voltage output for controlling the auxiliary boiler or alarm signalling or hot usable water circulation pump RELAY relay L N...

Страница 29: ...t to the temperature not exceeding 100 C 13 9 Connecting weather sensor The regulator cooperates only with a weather sensor of the CT6 P type The sensor should be installed on the coldest wall of the...

Страница 30: ...s Boiler Settings Pump off by therm 13 13 Connection of reserve boiler The regulator can control a reserve boiler gas or oil fired eliminating the necessity of enabling or disabling this boiler manual...

Страница 31: ...f boiler water is limited You are advised to get familiar with the position of the valve corresponding to its maximum opening before commencement of work so that you may ensure heat collection from th...

Страница 32: ...ck whether the valve is properly connected 13 16 Connecting temperature limiter STB In order to prevent the boiler from overheating due to the regulator malfunction an STB safety temperature limiter o...

Страница 33: ...ion method exhaust only water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max...

Страница 34: ...dditional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm...

Страница 35: ...n OPERATION mode cycle time Complete cycle time of fuel feeding in OPERATION mode OPERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg...

Страница 36: ...mum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regulator resumes normal oper...

Страница 37: ...es on the hot usable water pump and opens the mixer circuits in order to cool the boiler down The regulator will turn the hot usable water pump when the temperature of this water exceeds the maximum v...

Страница 38: ...oiler is on a satisfactory level the regulator will not change it in order to load the HUW tank buffer or mixer circuit The increase of the set boiler temperature for the period of loading the HUW tan...

Страница 39: ...uator Thermostat select Options to choose from Shut down it cuts the influence of room thermostat upon the boiler operation Universal it turns on the no nc room thermostat coupled to 42 43 contacts it...

Страница 40: ...emperature in the mixer circuit sensor is equal to the set temperature In order to avoid frequent actuator movements which can wear it down unnecessarily the parameter should only be regulated when th...

Страница 41: ...ecoTOUCH control panel from the regulator housing Insert memory card into indicated slot Memory card should contain new software stored in the pfc format two files one with software for control panel...

Страница 42: ...should be connected also when in the boiler is not in use This function can be enabled also when the regulator is turned off via keyboard regulator in STAND BY 17 4 Bunker feeder After connecting an a...

Страница 43: ......

Страница 44: ......

Страница 45: ......

Страница 46: ......

Страница 47: ......

Страница 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Отзывы: