9
MENU SELECTIONS
Notation Conventions for the Menus
Because of the number of features available in this
control, information is included that may not apply to your
specific control. All usable features are included in this
book, but may not be used in your process. To increase
clarity the following conventions are used:
1. Certain features or functions shown in this book are
contextual. This means that Menu Items may or may
not appear, depending on other Menu Item
selections. Whenever this occurs, a notation is made
in the Menu Item that ˝controls˝ or ˝directs˝ other
menu items. If you are looking for a particular menu
item and can’t find it, check the menu item that is its
˝control˝ for proper setting.
2. The ˝#˝ symbol is used in two ways. It is used inside
a group of characters to indicate which set point
function (SP1 or SP2) is being affected. It is also used
before a group of characters of a menu item to
indicate that there may be more than one selection or
value for that menu item.
Secondary Menu
Press the
INDEX key for 2 seconds to start the menu.
Press
INDEX to advance to the next menu item.
Press
UP ARROW or
DOWN ARROW to change
the value in the display. Press
ENTER to retain the
value.
SP1H
Pump 1 On Set Point. Factory Default
23.1
(feet).
SP1L
Pump 1 Off Set Point. Factory Default
0.0
(feet).
SP2H
Pump 2 On Set Point. Factory Default
23.1
(feet).
SP2L
Pump 2 Off Set Point. Factory Default
0.0
(feet).
A1Hi
Alarm 1 High: Factory Default
23.1
(feet).
A2Lo
Alarm 2 Low: Factory Default
2.0
(feet).
SFS1
Pump 1 Seal Failure Set Point: Select 10 to 500
in any increment of 10. Sets the resistance set
point at which the controller will trip the Seal
Failure based on the input from the pump
moisture sensor. The controller will activate the
Seal Failure condition based on a decrease of
resistance to the set point. Selectable resistance
range is from 10K to 500K Ω with the factory
default at 120K Ω.
SFS2
Pump 2 Seal Failure Set Point: Select 10 to 500
in any increment of 10. Sets the resistance set
point at which the controller will trip the Seal
Failure based on the input from the pump
moisture sensor. The controller will activate the
Seal Failure condition based on a decrease of
resistance to the set point. Selectable resistance
range is from 10K to 500K Ω with the factory
default at 120K Ω.
P1rn
Pump 1 Run Time: Total ON Time for Pump 1 in
HOURS since last reset (0000 - 9999 hours).
P2rn
Pump 2 Run Time: Total ON Time for Pump 2 in
HOURS since last reset (0000 - 9999 hours).
P1SF
Pump 1 Reset for Seal Failure. Displays ˝----˝
when pump 1 is in normal operating condition
based on seal failure input. Displays
FA1L
if
pump 1 has met the condition of a seal failure.
Press the ENTER key to reset. If pump 1 seal
failure is still in the fail condition then the control
will not reset. If the seal failure input is no longer
in fail condition then the display will revert to ˝----˝.
P2SF
Pump 2 Reset for Seal Failure. Displays ˝----˝
when pump 2 is in normal operating condition
based on seal failure input. Displays
FA1L
if
pump 2 has met the condition of seal failure.
Press the ENTER key to reset. If pump 2 seal
failure is still in the fail condition then the control
will not reset. If the seal failure input is no longer
in fail condition then the display will revert to ˝----˝.
P10t
Pump 1 Reset for Over Temperature. Displays
˝----˝ when pump 1 is in normal operating condition
based on temperature input. Displays
FA1L
if
pump 1 has met the condition of over temperature.
Press the ENTER key to reset. If pump 1
temperature input is still in the fail condition then
the control will not reset. If the temperature input
is no longer in fail condition then the display will
revert to ˝----˝.
P20t
Pump 2 Reset for Over Temperature. Displays
˝----˝ when pump 2 is in normal operating
condition based on temperature input. Displays
FA1L
if pump 2 has me the condition of over
temperature. Press the ENTER key to reset. If
pump 2 temperature input is still in the fail condition
then the control will not reset. If the temperature
input is no longer in fail condition then the display
will revert to ˝----˝.