background image

8

In  the  Secure  menu  the  value  of 

PSF

  is  programmed 

for  the  action  of  the  MPC  based  on  the  condition  of  a 

seal failure. If set to ˝

AUt0

˝ when pump moisture sensor 

indicates  that  there  is  a  seal  failure  condition  then 

the  corresponding  pump  seal  failure  lamp  is  lit  on  the 

controller. The pump will remain in service with only the 

lamp  indication  of  failure.  The  lamp  will  be  turned  off 

automatically when the seal failure condition has ceased. 

If 

PSF

  is  set  to  ˝

rES

˝  when  pump  moisture  sensor 

indicates  that  there  is  a  seal  failure  condition  then 

the  corresponding  pump  seal  failure  lamp  is  lit  on  the 

controller. If the MPC is only being used with one pump 

or being used with two pumps with the lead/lag function 

turned off then no action is taken by the MPC with the 

operation of the pumps. The failure indication lamp will 

be manually reset as described in the next paragraph. If 

the MPC is being used with two pumps with the lead/lag 

function turned on then the failed pump will automatically 

become the lag pump, the remaining pump will become 

the lead pump, and the alternation will be discontinued. 

The  lamp  indication  and  pump  alternation  can  be 

manually reset as described in the next paragraph.

Once  the  pump  has  been  repaired  the  seal  failure 

action  can  be  reset  with  the  values  of 

P1SF

  and 

P2SF

 in 

the Secondary menu. The item 

P1SF

 or 

P2SF

 will display 

FA1L

 if the corresponding pump has met the condition of 

a seal failure. Press the 

 ENTER key to reset. If the 

pump moisture sensor is still in the fail condition then the 

control will not reset. If the moisture sensor is no longer 

in the fail condition then the display will revert to ˝----˝.

OVER TEMPERATURE OPERATION

Most  pumps  have  an  installed  normally  closed 

thermostat for over temperature protection of the pump. 

The  thermostat  has  a  preset  value  from  the  pump 

manufacturer at which point the pump needs to be shut 

down. The Mercoid

®

 MPC detects when the thermostat 

signal changes to open and shuts down the pump. 

In the Secure menu the value of 

P0t

 is programmed for 

the  action  of  the  MPC  based  on  the  condition  of  the 

over temperature. When the pump temperature sensor 

indicates that there is an over temperature condition the 

pump will be held out of service and the corresponding 

pump  over  temperature  lamp  is  lit  on  the  controller.  If 

using the MPC with two pumps with the lead/lag function 

turned  on  then  the  failed  pump  will  automatically  be 

taken  out  of  service,  the  remaining  pump  will  become 

the lead pump, and the alternation will be discontinued. 

When controlling two pumps with the lead/lag function off 

the failed pump will automatically be taken out of service 

and the remaining pump will be controlled by the 

SP1H

 and 

SP1L

 set points.

If 

P0t

 is set to ˝

AUt0

˝ then the pump will be automatically 

placed back into service and the lamp turned off when 

the  over  temperature  condition  has  ceased.  If  set  to 

˝

rES

 ˝ then the pump will remain out of service and the 

lamp  lit  until  the  corresponding  manual  reset 

P10t

 or 

P20t

  is  reset  in  the  Secondary  menu  (described  in  the 

next paragraph). The pump cannot be brought back into 

service until the over temperature condition has ceased.

Once  the  pump  has  cooled  down  the  MPC  Pump 

Controller  can  be  reset  with  the  values  of 

P10t

  and 

P20t

  in  the  Secondary  menu. The  item 

P10t

 or 

P20t

 will 

display 

FA1L

  if  the  pump  has  met  the  condition  of  over 

temperature.  Press  the 

  ENTER  key  to  reset.  If  the 

pump temperature sensor is still in the fail condition then 

the control will not reset. If the temperature input is no 

longer in the fail condition then the display will revert to 

˝----˝.

ANALOG RETRANSMISSION OPERATION

The analog retransmission allows the Process Variable 

to  be  sent  as  an  analog  signal  to  an  external  device. 

The signal may be either 2-10 VDC (option RV) or 4-20 

mADC  (standard).  The  output  may  be  changed  in  the 

field from one to the other by the toggle switch located on 

the top printed circuit board, factory standard is mADC.

Wire the output as shown on page 1.

To set up the analog retransmission, first determine the 

scale  range  that  the  analog  signal  will  represent.  The 

maximum  scale  is  9999  counts.  In  the  Secure  menu 

set 

P0L

  for  the  scale  value  that  will  be  represented  by 

the low end of the analog signal (2 V or 4 mA). Set 

P0H

 

for the scale value that will be represented by the high 

end  of  the  analog  signal  (10  V  or  20  mA).  Operation 

is  automatic.  There  are  no  further  programming  steps 

required. The values of 

P0L

 and 

P0H

 must be within the 

programmed scale range. The scale range is set by the 

SCAL

 and 

SCAH

 in the Secure menu.

PUMP RUN TIME OPERATION

The  pump  run  time  is  indicated  in  hours  of  operation 

since  the  last  time  that  the  run  time  meter  was  reset 

for a specific pump. The   Pump Run Time key on the 

front of the unit will display run time for both pumps when 

depressed. Run time for pump 1 is in the top display and 

pump  2  is  in  the  lower  display. To  reset  the  pump  run 

time go to the menu items 

P1rn

 and 

P2rn

 in the Secondary 

Menu.  When  in  the  corresponding  menu  item  hold  the 

 ENTER button for approximately two seconds. The 

display will blank out for about 1 second and the run time 

will display 0. These menu items can be locked out by 

the 

PrSt

 menu item in the Secure Menu.

OPTION 232, 485 SERIAL COMMUNICATION 

OPERATION

The serial communications options allow the control to 

be written to and read from a remote computer or other 

similar  digital  device.  Communication  is  allowed  either 

through a RS-485 (Option 485) port, or a RS-232 (Option 

232) port. 

Wire  the  communication  lines  as  shown  on  page  5. 

Wiring  for  the  RS-485  is  run  from  control  to  control  in 

a  daisy  chain  fashion  with  a  termination  resistor  (120 

Ω) across the transmit and receive terminals of the last 

control in the chain. Set the RS-485 DIP switch for half 

or full duplex as appropriate for your application. The DIP 

switch is located on the communications board plugged 

into the center of the bottom board of the control.

Select  the  control  address  and  communication  baud 

rate with the Addr and bAUd menu items in the Secure 

Menu. THE BAUD RATE AND ADDRESS MENU ITEMS 

WILL  TAKE  EFFECT  ON  THE  NEXT  POWER  UP  OF 

THE  CONTROL.  BE  SURE  TO  POWER  CYCLE  THE 

CONTROL  BEFORE  USING  THE  NEW  BAUD  RATE 

AND ADDRESS.

In operation, you have the option of preventing a write 

command from the host computer. To prevent the host 

from writing to the control change the L0rE menu item in 

the Secondary Menu to L0C. To allow the host to write 

commands to the control set L0rE to rE. (The host does 

have  the  ability  to  change  the  L0rE  state,  but  it  is  not 

automatic.)

If  your  system  depends  on  constant  reading  or  writing 

to and from the host, you may wish to set the No Activity 

Timer  (

nAt

)  to  monitor  the  addressing  of  the  control. 

When the 

L0rE

 is set to 

rE

 and the 

nAt

 is set to any value 

other than 

0FF

, the control will expect to be addressed 

on a regular basis. If the control is not addressed in the 

time set by the value of 

nAt

, then the control will display 

the error message 

CHEC

 

LorE

. To clear the message set 

L0rE

 to 

L0C

.

www.

.com

[email protected]

1.800.561.8187

Содержание Series MPC

Страница 1: ...NPN open collector type Current 1 mADC Isolation Shares common ground with transmitter input Alarm On Off Differential 1 count Set Point Range Selectable Power Voltage Stability 0 05 over the power voltage range Temperature Stability 100 PPM C typical 200 PPM C maximum Common Mode Rejection 140 db minimum at 60 Hz Normal Mode Rejection 65 db typical 60 db at 60 Hz Isolation Relay 1500 VAC to all o...

Страница 2: ...n see Specifications for specific tolerances All models are designed for mounting in an enclosed panel Select the position desired for the instrument on the panel Prepare the panel by cutting and deburring the required opening From the front of the panel slide the housing through the cut out The housing gasket should be against the housing flange before installing From the rear of the panel slide ...

Страница 3: ...puts then jumper terminals 22 to 23 and 22 to 24 Figure 2 Wiring PUMP 1 OVER TEMP PUMP 2 OVER TEMP VOLTAGE CURRENT SEAL SENSOR INPUTS PUMP1 ALARM 1 CONTACTS ALARM 2 CONTACTS PUMP 1 OUTPUT PUMP 2 OUTPUT 24 VDC 50 MA ISOLATED PUMP2 N O COM N O COM N C COM N O N C COM N O NOTES 1 FOR SUPPLY CONNECTIONS USE NO 16 AWG OR LARGER WIRES RATED FOR AT LEAST 167 F 75 C OR IN ACCORDANCE WITH AN EQUIVALENT NAT...

Страница 4: ...structions provided with your transmitter CONNECT JUMPER BETWEEN TERMINALS 2 AND 12 LEVEL TRANSMITTER CONNECT TRANSMITTER PLUS TO TERMINAL 11 CONNECT TRANSMITTER MINUS TO TERMINAL 3 1 22 23 24 25 26 21 28 29 30 31 32 27 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Figure 3 Transmitter wiring DO NOT wire the 24 V Power Supply across the input of the control Damage to the control input circuitry...

Страница 5: ...nsmit Data in For half duplex operation wire only A and B Do not connect to Y and Z 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 DATA IN 30 DATA OUT 32 DATA GROUND 31 PIN DESCRIPTION 1 SHIELD 2 TRANSMIT 3 RECEIVE 4 RTS 5 CTS PIN DESCRIPTION 6 DSR 7 GROUND 8 DCD 20 DTR DB 25 WIRING VIEWED FROM WIRE SIDE 1 2 3 4 5 6 7 8 9 RS 232 DB 9 WIRING VIEWED FROM WIRE SIDE PIN DESCRIPTION ...

Страница 6: ...obtainable is 9999 regardless of decimal point placement DOWN ARROW Decrements a value changes a menu item or selects the item to OFF The minimum value obtainable is 1999 regardless of decimal point placement ENTER The ENTER key is used to store the value of menu items once they are changed to a new value If the ENTER key is not pressed after changing the value the item will revert to the previous...

Страница 7: ...on to minimize wear The Mercoid MPC pump controller has a pair of set points each for pump 1 and pump 2 If the lead lag feature is turned off SP1H and SP1L control pump 1 and SP2H and SP2L control pump 2 If the lead lag feature is turned on pumps 1 and 2 will be controlled in the alternating fashion described below In all cases the P1 lamp will indicate activity of pump 1 and the P2 lamp will indi...

Страница 8: ...e sensor is still in the fail condition then the control will not reset If the temperature input is no longer in the fail condition then the display will revert to ANALOG RETRANSMISSION OPERATION The analog retransmission allows the Process Variable to be sent as an analog signal to an external device The signal may be either 2 10 VDC option RV or 4 20 mADC standard The output may be changed in th...

Страница 9: ...00 in any increment of 10 Sets the resistance set point at which the controller will trip the Seal Failure based on the input from the pump moisture sensor The controller will activate the Seal Failure condition based on a decrease of resistance to the set point Selectable resistance range is from 10K to 500K Ω with the factory default at 120K Ω P1rn Pump 1 Run Time Total ON Time for Pump 1 in HOU...

Страница 10: ...following Refer to the Input wiring section for the proper wiring Factory Default is Curr Curr DC Current Input 0 0 to 20 0 or 4 0 to 20 0 mA UoLt DC Voltage Input 0 0 to 10 0 or 2 0 to 10 0 volts Reserved P0t Pump Over Temperature Select AUt0 or rES When pump temperature sensor indicates that there is an over temperature condition the pump will be held out of service and the corresponding pump ov...

Страница 11: ...rE is programmed for Hold the alarm will automatically reset upon a power failure and subsequent restoration if no alarm condition is present If Alarm Inhibit A iH is selected ON an alarm condition is suspended upon power up until the process value passes through the alarm set point once Alarm inhibit can be restored as if a power up took place by pressing both the INDEX and ENTER keys for 5 secon...

Страница 12: ...sed A2td Alarm 2 time Delay Select 0FF or 1 to 8000 seconds Factory default is 0FF 0FF Alarm function will operate when triggered at programmed Alarm Set Point 1 8000 Alarm function will only operate once the programmed time has elapsed after the alarm was triggered by the Alarm Set Point FiLt Digital Filter Select 0FF or 1 to 99 In some cases the time constant of the sensor or noise could cause t...

Страница 13: ...utputs active Alarms active Input signals may normally go above or below range ends If not check input and correct CHEC CAL Check calibration appears as an alternating message if the instrument calibration nears tolerance edges Check calibration appears as a flashing message if the instrument calibration exceeds specification Set point outputs active Alarms active Set point outputs inactive Alarms...

Страница 14: ... Pump Over Temperature controller action selectable automatic or manual reset Pump Seal Failure controller action selectable automatic or manual reset System Test Selectable on or off Pump Run Time Rest Selectable on or off Set Point High value default is in feet Set Point Low value default is in feet Peak highest input value seen since last reset Valley lowest input value seen since last reset Al...

Страница 15: ...electable onof auto or hold manual Alarm 1 Power Interrupt selectable on or off Alarm 1 Inhibit selectable on or off Alarm 1 Output State selectable close or open Alarm 1 Lamp condition when contact is closed selectable on or off Alarm 1 Time Delay selectable off or 1 to 8000 s Alarm 2 function selectable off lo hi hilo sf ot or sfot Alarm 2 Type selectable abs absolute or de deviation Alarm 2 Res...

Страница 16: ...____________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ _____________________________...

Отзывы: