10

Secure Menu

Press the   INDEX key for 5 seconds to start the menu. 

Press 

  INDEX  to  advance  to  the  next  menu  item. 

Press 

 UP ARROW or 

 DOWN ARROW to change 

the value in the display. Press 

ENTER to retain the 

value.  OUTPUTS  ARE  DISABLED  (TURNED  OFF) 

WHILE CONTROL IS IN THE SECURE MENU.

SECr

  Security Code: See the Security Level Selection 

      and the Password Table on page 7, in order to 

      enter the correct password. Factory Default is 

4

.

SCAH

  Scale High: Select 

100

 to 

9999

 counts above 

SCAL

      The total span between 

SCAL

 and 

SCAH

 must be 

      within 11998 counts. Maximum setting range is 

   

-1999

 to 

+9999

 counts. Factory Default is 

23.1

.

SCAL

  Scale Low: Select 

100

 to 

9999

 counts below 

SCAH

      The total span between 

SCAL

 and 

SCAH

 must be 

      within 11998 counts. Maximum setting range is 

   

-1999

 to 

+9999

 counts. Factory Default is 

0.0

.

dPt   Decimal Point Positioning: Select 

0

,

 0.0

0.00

, or 

   

0.000

. All Menu items related to the input will be 

      affected. Factory default is

 0.0

.

S1St

   Set Point 1 State: Select 

P1n

 or 

P0ut

. Factory 

      default is 

P0ut

.

   

P1n

    Pump In (Direct Action). As the input 

              increases the output will increase.

   

P0ut

    Pump Out (Reverse Action). As the input 

              increases the output will decrease.

S2St

  Set Point 2 State: Select 

P1n

P0ut

 or 

0FF

. Factory 

      default is 

P0ut

.

   

P1n

    Pump In (Direct Action). As the input 

              increases the output will increase.

   

P0ut

    Pump Out (Reverse Action). As the input 

              increases the output will decrease.

   

0FF

     This setting is for applications when the 

              MPC is used with only one pump systems. 

              All Menu tems relating to Set Point 2 will not 

       appear.

LdL9

  Lead / Lag: Select 

0n

 or 

0FF

. Factory default is 

0n

      (See page 7) 

   

0n

    The Lead/Lag function is enabled. The outputs 

            of 

SP1

 and 

SP2

 will alternate. 

   

0FF

   The Lead/Lag function is disabled.

1nPC

   Input Correction: Select ±500 counts. This feature 

      allows the input value to be changed to agree 

      with an external reference or to compensate for 

   sensor error. 

Note: 

1nPC

 is reset to zero when 

      the input type is changed, or when decimal position 

      is changed.

0SUP

  Zero Suppression: Select 

0n

 or 

0FF

. Factory default 

   is 

0n

.

   

0FF

   The input range will start at 0 (zero) Input.

   

0n

    The input range will start at 4.00 mA or 2.00 V.

1nP

  Input Type: Select one of the following. Refer to the 

      Input wiring section for the proper wiring. Factory 

      Default is 

Curr

.

   

Curr

    DC Current Input 0.0 to 20.0 or 4.0 to 20.0 

       mA.

   

UoLt

    DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0  

              volts.

      - - - -   Reserved

P0t

   Pump Over Temperature: Select 

AUt0

 or 

rES

      When pump temperature sensor indicates that 

      there is an over temperature condition the pump will 

      be held out of service and the corresponding pump 

      over temperature lamp is lit on the controller. If 

      using the MPC with two pumps and lead/lag on

      then the remaining pump becomes the lead pump. 

      If lead/lag is turned off then the remaining pump 

      becomes controlled by Set Point 1. See page 8.

   

AUt0

    The pump will be automatically placed back 

              into service and the lamp turned off when 

              the over temperature condition has ceased.

   

rES

     The pump will remain out of service and the 

              lamp lit until the corresponding manual reset 

       

P10t

 or 

P20t

 is reset in the Secondary menu. 

              The pump cannot be brought back into 

              service until the over temperature condition 

              has ceased. 

 

PSF

   Pump Seal Failure: Select 

AUt0

 or 

rES

. See pages 

      7 and 8.

   

AUt0

    When pump moisture sensor indicates that 

              there is a seal failure condition the 

              corresponding pump seal failure lamp is lit 

              on the controller. The pump will remain in 

              service with only the lamp indication of 

              failure. The lamp will automatically turn off 

              when failure condition ceases.

   

rES

     When pump moisture sensor indicates that 

              there is a seal failure condition the 

              corresponding pump seal failure lamp is lit 

              on the controller. If the MPC is being used 

              with two pumps and the lead/lag feature 

              turned on then the failed pump will 

              automatically become the lag pump, the 

              remaining pump the lead pump, and the 

              alternation discontinued. The seal failure 

              action  is  reset  manually  with  the  values  of 

 

       

P1SF

  and 

P2SF

  in  the  Secondary  menu.  The 

 

              control will only reset if the pump moisture 

 

              sensor is no longer in a failed condition. 

tESt

  System Test: Select 

0n

 or 

0FF

. When 

0n

 is selected 

      the ˝System Test˝ key on the front panel will be 

      activated. By depressing this key for 3 seconds the 

      controller will simulate an input from 

SCAL

 to 

SCAH

 

      and back to 

SCAL

 over a period of 32 seconds. This 

      test will run continuously until the SYSTEM TEST 

      key is pressed again. When the controller is in 

      System Test Mode the lamp above the System Test 

      Key will be ON.

www.

.com

[email protected]

1.800.561.8187

Содержание Series MPC

Страница 1: ...NPN open collector type Current 1 mADC Isolation Shares common ground with transmitter input Alarm On Off Differential 1 count Set Point Range Selectable Power Voltage Stability 0 05 over the power voltage range Temperature Stability 100 PPM C typical 200 PPM C maximum Common Mode Rejection 140 db minimum at 60 Hz Normal Mode Rejection 65 db typical 60 db at 60 Hz Isolation Relay 1500 VAC to all o...

Страница 2: ...n see Specifications for specific tolerances All models are designed for mounting in an enclosed panel Select the position desired for the instrument on the panel Prepare the panel by cutting and deburring the required opening From the front of the panel slide the housing through the cut out The housing gasket should be against the housing flange before installing From the rear of the panel slide ...

Страница 3: ...puts then jumper terminals 22 to 23 and 22 to 24 Figure 2 Wiring PUMP 1 OVER TEMP PUMP 2 OVER TEMP VOLTAGE CURRENT SEAL SENSOR INPUTS PUMP1 ALARM 1 CONTACTS ALARM 2 CONTACTS PUMP 1 OUTPUT PUMP 2 OUTPUT 24 VDC 50 MA ISOLATED PUMP2 N O COM N O COM N C COM N O N C COM N O NOTES 1 FOR SUPPLY CONNECTIONS USE NO 16 AWG OR LARGER WIRES RATED FOR AT LEAST 167 F 75 C OR IN ACCORDANCE WITH AN EQUIVALENT NAT...

Страница 4: ...structions provided with your transmitter CONNECT JUMPER BETWEEN TERMINALS 2 AND 12 LEVEL TRANSMITTER CONNECT TRANSMITTER PLUS TO TERMINAL 11 CONNECT TRANSMITTER MINUS TO TERMINAL 3 1 22 23 24 25 26 21 28 29 30 31 32 27 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Figure 3 Transmitter wiring DO NOT wire the 24 V Power Supply across the input of the control Damage to the control input circuitry...

Страница 5: ...nsmit Data in For half duplex operation wire only A and B Do not connect to Y and Z 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 DATA IN 30 DATA OUT 32 DATA GROUND 31 PIN DESCRIPTION 1 SHIELD 2 TRANSMIT 3 RECEIVE 4 RTS 5 CTS PIN DESCRIPTION 6 DSR 7 GROUND 8 DCD 20 DTR DB 25 WIRING VIEWED FROM WIRE SIDE 1 2 3 4 5 6 7 8 9 RS 232 DB 9 WIRING VIEWED FROM WIRE SIDE PIN DESCRIPTION ...

Страница 6: ...obtainable is 9999 regardless of decimal point placement DOWN ARROW Decrements a value changes a menu item or selects the item to OFF The minimum value obtainable is 1999 regardless of decimal point placement ENTER The ENTER key is used to store the value of menu items once they are changed to a new value If the ENTER key is not pressed after changing the value the item will revert to the previous...

Страница 7: ...on to minimize wear The Mercoid MPC pump controller has a pair of set points each for pump 1 and pump 2 If the lead lag feature is turned off SP1H and SP1L control pump 1 and SP2H and SP2L control pump 2 If the lead lag feature is turned on pumps 1 and 2 will be controlled in the alternating fashion described below In all cases the P1 lamp will indicate activity of pump 1 and the P2 lamp will indi...

Страница 8: ...e sensor is still in the fail condition then the control will not reset If the temperature input is no longer in the fail condition then the display will revert to ANALOG RETRANSMISSION OPERATION The analog retransmission allows the Process Variable to be sent as an analog signal to an external device The signal may be either 2 10 VDC option RV or 4 20 mADC standard The output may be changed in th...

Страница 9: ...00 in any increment of 10 Sets the resistance set point at which the controller will trip the Seal Failure based on the input from the pump moisture sensor The controller will activate the Seal Failure condition based on a decrease of resistance to the set point Selectable resistance range is from 10K to 500K Ω with the factory default at 120K Ω P1rn Pump 1 Run Time Total ON Time for Pump 1 in HOU...

Страница 10: ...following Refer to the Input wiring section for the proper wiring Factory Default is Curr Curr DC Current Input 0 0 to 20 0 or 4 0 to 20 0 mA UoLt DC Voltage Input 0 0 to 10 0 or 2 0 to 10 0 volts Reserved P0t Pump Over Temperature Select AUt0 or rES When pump temperature sensor indicates that there is an over temperature condition the pump will be held out of service and the corresponding pump ov...

Страница 11: ...rE is programmed for Hold the alarm will automatically reset upon a power failure and subsequent restoration if no alarm condition is present If Alarm Inhibit A iH is selected ON an alarm condition is suspended upon power up until the process value passes through the alarm set point once Alarm inhibit can be restored as if a power up took place by pressing both the INDEX and ENTER keys for 5 secon...

Страница 12: ...sed A2td Alarm 2 time Delay Select 0FF or 1 to 8000 seconds Factory default is 0FF 0FF Alarm function will operate when triggered at programmed Alarm Set Point 1 8000 Alarm function will only operate once the programmed time has elapsed after the alarm was triggered by the Alarm Set Point FiLt Digital Filter Select 0FF or 1 to 99 In some cases the time constant of the sensor or noise could cause t...

Страница 13: ...utputs active Alarms active Input signals may normally go above or below range ends If not check input and correct CHEC CAL Check calibration appears as an alternating message if the instrument calibration nears tolerance edges Check calibration appears as a flashing message if the instrument calibration exceeds specification Set point outputs active Alarms active Set point outputs inactive Alarms...

Страница 14: ... Pump Over Temperature controller action selectable automatic or manual reset Pump Seal Failure controller action selectable automatic or manual reset System Test Selectable on or off Pump Run Time Rest Selectable on or off Set Point High value default is in feet Set Point Low value default is in feet Peak highest input value seen since last reset Valley lowest input value seen since last reset Al...

Страница 15: ...electable onof auto or hold manual Alarm 1 Power Interrupt selectable on or off Alarm 1 Inhibit selectable on or off Alarm 1 Output State selectable close or open Alarm 1 Lamp condition when contact is closed selectable on or off Alarm 1 Time Delay selectable off or 1 to 8000 s Alarm 2 function selectable off lo hi hilo sf ot or sfot Alarm 2 Type selectable abs absolute or de deviation Alarm 2 Res...

Страница 16: ...____________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ _____________________________...

Отзывы: