10
Secure Menu
Press the INDEX key for 5 seconds to start the menu.
Press
INDEX to advance to the next menu item.
Press
UP ARROW or
DOWN ARROW to change
the value in the display. Press
ENTER to retain the
value. OUTPUTS ARE DISABLED (TURNED OFF)
WHILE CONTROL IS IN THE SECURE MENU.
SECr
Security Code: See the Security Level Selection
and the Password Table on page 7, in order to
enter the correct password. Factory Default is
4
.
SCAH
Scale High: Select
100
to
9999
counts above
SCAL
.
The total span between
SCAL
and
SCAH
must be
within 11998 counts. Maximum setting range is
-1999
to
+9999
counts. Factory Default is
23.1
.
SCAL
Scale Low: Select
100
to
9999
counts below
SCAH
.
The total span between
SCAL
and
SCAH
must be
within 11998 counts. Maximum setting range is
-1999
to
+9999
counts. Factory Default is
0.0
.
dPt Decimal Point Positioning: Select
0
,
0.0
,
0.00
, or
0.000
. All Menu items related to the input will be
affected. Factory default is
0.0
.
S1St
Set Point 1 State: Select
P1n
or
P0ut
. Factory
default is
P0ut
.
P1n
Pump In (Direct Action). As the input
increases the output will increase.
P0ut
Pump Out (Reverse Action). As the input
increases the output will decrease.
S2St
Set Point 2 State: Select
P1n
,
P0ut
or
0FF
. Factory
default is
P0ut
.
P1n
Pump In (Direct Action). As the input
increases the output will increase.
P0ut
Pump Out (Reverse Action). As the input
increases the output will decrease.
0FF
This setting is for applications when the
MPC is used with only one pump systems.
All Menu tems relating to Set Point 2 will not
appear.
LdL9
Lead / Lag: Select
0n
or
0FF
. Factory default is
0n
.
(See page 7)
0n
The Lead/Lag function is enabled. The outputs
of
SP1
and
SP2
will alternate.
0FF
The Lead/Lag function is disabled.
1nPC
Input Correction: Select ±500 counts. This feature
allows the input value to be changed to agree
with an external reference or to compensate for
sensor error.
Note:
1nPC
is reset to zero when
the input type is changed, or when decimal position
is changed.
0SUP
Zero Suppression: Select
0n
or
0FF
. Factory default
is
0n
.
0FF
The input range will start at 0 (zero) Input.
0n
The input range will start at 4.00 mA or 2.00 V.
1nP
Input Type: Select one of the following. Refer to the
Input wiring section for the proper wiring. Factory
Default is
Curr
.
Curr
DC Current Input 0.0 to 20.0 or 4.0 to 20.0
mA.
UoLt
DC Voltage Input 0.0 to 10.0 or 2.0 to 10.0
volts.
- - - - Reserved
P0t
Pump Over Temperature: Select
AUt0
or
rES
.
When pump temperature sensor indicates that
there is an over temperature condition the pump will
be held out of service and the corresponding pump
over temperature lamp is lit on the controller. If
using the MPC with two pumps and lead/lag on
then the remaining pump becomes the lead pump.
If lead/lag is turned off then the remaining pump
becomes controlled by Set Point 1. See page 8.
AUt0
The pump will be automatically placed back
into service and the lamp turned off when
the over temperature condition has ceased.
rES
The pump will remain out of service and the
lamp lit until the corresponding manual reset
P10t
or
P20t
is reset in the Secondary menu.
The pump cannot be brought back into
service until the over temperature condition
has ceased.
PSF
Pump Seal Failure: Select
AUt0
or
rES
. See pages
7 and 8.
AUt0
When pump moisture sensor indicates that
there is a seal failure condition the
corresponding pump seal failure lamp is lit
on the controller. The pump will remain in
service with only the lamp indication of
failure. The lamp will automatically turn off
when failure condition ceases.
rES
When pump moisture sensor indicates that
there is a seal failure condition the
corresponding pump seal failure lamp is lit
on the controller. If the MPC is being used
with two pumps and the lead/lag feature
turned on then the failed pump will
automatically become the lag pump, the
remaining pump the lead pump, and the
alternation discontinued. The seal failure
action is reset manually with the values of
P1SF
and
P2SF
in the Secondary menu. The
control will only reset if the pump moisture
sensor is no longer in a failed condition.
tESt
System Test: Select
0n
or
0FF
. When
0n
is selected
the ˝System Test˝ key on the front panel will be
activated. By depressing this key for 3 seconds the
controller will simulate an input from
SCAL
to
SCAH
and back to
SCAL
over a period of 32 seconds. This
test will run continuously until the SYSTEM TEST
key is pressed again. When the controller is in
System Test Mode the lamp above the System Test
Key will be ON.