15
Menu
Item
Default Set At
Description
Secondary
SP1H
SP1L
SP2H
SP2L
A1Hi
A2Lo
SFS1
SFS2
P1rn
P2rn
P1SF
P2SF
P1OT
P2OT
23.1
0.0
23.1
0.0
23.1
2.0
120
120
xxxx
xxxx
----
----
----
----
6.0
3.0
12.0
9.0
20.0
1.0
120
120
Set Point 1 value (default is in feet)
Set Point 1 off value (default is in feet)
Set Point 2 value (default is in feet)
Set Point 2 off value (default is in feet)
Alarm 1 (high) value (default is in feet)
Alarm 2 (low) value (default is in feet)
Pump 1 Seal Failure Set Point
Pump 2 Seal Failure Set Point
Total ON Time for Pump 1 in HOURS since last reset
Total ON Time for Pump 2 in HOURS since last reset
Pump 1 Reset for Seal Failure (---- or FAIL)
Pump 2 Reset for Seal Failure (---- or FAIL)
Pump 1 Reset for Over Temperature (---- or FAIL)
Pump 2 Reset for Over Temperature (---- or FAIL)
Secure
ALI
ALt
AIrE
AIPi
AIiH
AISt
AILP
AItd
AL2
A2t
A2rE
A2Pi
A2iH
R2St
A2LP
A2td
FILt
POH
POL
Hi
AbS
OnOF
OFF
OFF
CLOS
Oon
OFF
Lo
AbS
OnOF
OFF
OFF
CLOS
Oon
OFF
3
23.1
0.0
Hi
AbS
OnOF
OFF
OFF
CLOS
Oon
OFF
Lo
AbS
OnOF
OFF
OFF
CLOS
Oon
OFF
3
25.0
0.0
Alarm 1 Function (selectable off, lo, hi, hilo, sf, ot, or sfot)
Alarm Type 1 (selectable abs (absolute) or de (deviation))
Alarm 1 Reset (selectable onof (auto) or hold (manual))
Alarm 1 Power Interrupt (selectable on or off)
Alarm 1 Inhibit (selectable on or off)
Alarm 1 Output State (selectable close or open)
Alarm 1 Lamp condition when contact is closed (selectable on or off)
Alarm 1 Time Delay (selectable off or 1 to 8000 s)
Alarm 2 function ( selectable off, lo, hi, hilo, sf, ot, or sfot)
Alarm 2 Type (selectable abs (absolute) or de (deviation))
Alarm 2 Reset (selectable onof (auto) or hold (manual))
Alarm 2 Power Interrupt (selectable on or off)
Alarm 2 Inhibit (selectable on or off)
Alarm 2 Output State (selectable close or open)
Alarm 2 Lamp condition when contact is closed (selectable on or off)
Alarm 2 Time Delay (selectable Off or 1 to 8000 s)
Digital Filter
Process Output High (default is in feet)
Process Output Low (default is in feet)
PROGRAMMING EXAMPLE
MPC
PBLT OR LEVEL TRANSMITTER
HIGH LEVEL ALARM
LOW LEVEL ALARM
START 2
START 1
STOP 2
STOP 1
Example:
• Keep Empty, two pump (duplex)
• Depth 25 feet
• Pump 1: Start at 6 feet
Stop at 3 feet
Pump 2: Start at 12 feet
Stop at 9 feet
• Low level alarm: 1 foot, fixed,
auto reset
• High level alarm: 20 feet, fixed,
auto reset
• Want Lead/Lag function on
• Automatic reset of pump over
.
temperature and seal failure
• No communication options
• Want 4-20 mA retransmission
• Using with a 4-20 mA input.
EXAMPLE PROGRAMMING CHART
www.
.com
1.800.561.8187