10.5.3 Fitting the front panel
Fitting the front panel
A seal is located at the rear of the front panel.
This seal cannot be replaced. If the seal is dama-
ged, the front panel has to be replaced.
Fit the front panel (
1
) and use screws (
2
) to tighten.
11. Faults
11.1 Remedy
Course of action when circuit breakers or residual cur-
rent device (FI/RCDs) have been tripped
Possible causes that lead to the tripping of a
circuit breaker can involve, for example, residual
current or an overloaded electrical circuit.
Situation
A): A circuit breaker is triggered.
Course of action:
Visually inspect the power distribution box and the con-
nected electrical consumers for exterior damage.
YES - there is an apparent defect with the power distri-
bution box or a connected electrical consumer.
Course of action:
Take the affected consumer out of service.
or
Take the power distribution box out of service.
Charge a qualified electrician with inspection and repair.
NO - there is no apparent defect.
Disconnect the consumer of the tripped circuit from the
power distribution box.
Switch on the tripped circuit breaker again.