Gas Input Rate Verification
Natural Gas Input Rate Verification
1. Verify main orifice size. The main orifice body has the orifice hole size stamped on it. NG orifice size shall be 1/8
”
for
0-2000 ft and for 2000-5000f.
2. Verify that the Manifold Gas Pressure is within 3.5" WC +/-
1/8". Once setup, read the main home gas supply meter
reading.
3. Write the initial reading here >> initial gas meter reading
Turn off all other appliances and their pilot flame in the home.
4. Run this appliance for a period of 30 minutes on maximum flame size. Turn off main burner and pilot
flame. Read the main home gas supply meter reading after the 30 minutes of burn time.
5. Write the reading here >> final gas meter reading
Calculate the following:
6. FINAL GAS METER READING - INITIAL GAS METER READING...Subtract initial gas meter from final gas meter
reading. This will yield the number of Therms used during the 30-minute burn time.
7. Multiply the result in Item #6 by 100,000.
8. Multiply the result in Item #7 by 2. Write down the result here >>
9. The result in item #8 shall be at least the maximum input rate (41,000 Btu/Hr) for all altitudes.
LPG Input Rate Verification
Verify main orifice size. The main orifice body has the orifice hole size stamped on it. LPG orifice size shall be #49 (0-
2000ft) and for (2000-5000ft).
Verify that the manifold gas pressure is within 10.0" WC +/- 1/8".
High Altitude De-Rating
If you are de-rating this appliance at a high altitude, attach the High-Altitude De-Rating Label, supplied in the
Owner’s
Manual Packet, to the back surface of the listing label plate located in the air gap on the side of the Fireplace. If you
are also converting the Fireplace for LP Gas attach the labels included with the conversion kit to the same surface.
Prior to attaching the label, fill in all the information that is requested on the label.
For installations from 610-1370 meters (2000-4500 ft.) the orifice sizes (DMS) for Natural Gas is
1/8”
and Propane Gas is
#49. See data plate for additional information. For high altitude installations consult the local gas distributor or the
authority having jurisdiction for proper rating methods. If the installer must convert the unit to adjust for varying
altitudes, the information sticker must be filled out by the installer and adhered to the appliance at the time of
conversion."
This appliance has been converted for use at an altitude of:
Orifice size:
Manifold Pressure:
Input (Btu/h):
Fuel Type:
Date of conversion:
Converted by:
Cet appreeil a été converti au ____
Injecteur ________
Pression à la tubulure d'alimentation _____________
Déoit calorifique ______________
Содержание ML54
Страница 2: ...85 03 01145 ML54 HOMEOWNER NOTES...
Страница 16: ...85 03 01145 ML54 Page 16 Figure 4 11 Figure 4 10...
Страница 24: ...85 03 01145 ML54 Page 24 Clearance from Appliance Side Walls Figure 4 18 CLEARANCE TO BODY...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...