TECHNICAL REFERENCES
Read and understand all information provided under this section,
, before you begin the installation of this
product. Failure to follow all technical reference information, use of components or parts not approved or use of improper
installation procedures can lead to a fire or explosion causing property damage, personal injury or loss of life.
4.1
GENERAL TECHNICAL REFERENCES
Caution
: Before igniting the pilot or burners, perform the following inspections and verifications:
Check glass gasket seal. Visually inspect glass gasket, especially at the corners of the glass piece. Glass gasket is installed as a 4-
piece assembly. Check joints between the gasket pieces at the corners. They should butt against each other to create a seal.
Gaps between gasket pieces can cause exhaust leaks and lead to acrid smell concerns. Check for gas leaks at all fittings.
During the first burning cycle of this Fireplace, ensure the convection blower is running at level three during the first two hours
of initial burn. After two hours of initial burn, allow fireplace to cool.
This fireplace must be installed and serviced by a qualified installer, service agency, or the gas supplier. Any adjustments to
burner, pilot, logs or coal bed must be made by a qualified installer, service agency, or the gas supplier.
If ignition system goes into lockout mode, always wait 5 minutes before attempting to relight pilot.
Never block off convection air openings or paths. Trim panels or surrounds shall not seal ventilation openings in the fireplace.
Always use Mendota decorative fronts and Mendota approved vent systems and vent caps only.
Mendota Fireplace Curing Instructions
ATTENTION
It is important that the blowers are turned on during this step to prevent the curing smoke from staining the
wall finish above the fireplace. Mendota recommends completing Step 1 prior to install ation of wall finish
materials.
Visible smoke and strong odor are to be expected during this step. If desired, disable smoke alarms before
this step, smoke from the initial curing c ycle will set off smoke alarms. Open doors and windows of the home
to circulate fresh air.
Step 1: Expelling Initial Smoke and Odors
Please refer to OPERATING INFORMATION if you have questions on how to operate your Mendota.
•
Complete the installation of any barrier screen (required) or front.
•
Turn the fireplace on in the Manual (Off) thermostat mode.
•
Set the Flame Height to Hi.
•
Set the Fan Speed Control to Level 3.
•
Run the fireplace with these settings for a minimum of 2 hours.
•
Turn the fireplace off and let it cool.
Step 2: High Heat Curing Cycle
•
Turn the fireplace on in the Manual (Off) thermostat mode.
•
Set the Flame Height to Hi.
•
Set the Fan Speed Control to Off.
•
Run the fireplace with these settings until curing odors have diminished.
•
When odors have diminished leave the fireplace turned on and continue to Step 3.
WARNING
FIRE RISK/ODOR RISK
•
This fireplace must be installed on top of wood, masonry or metal floor extending the full width and depth of this
fireplace.
•
Verify glass gasket seal before firing unit the first time. Verify proper latching of glass frame onto unit body.
•
Understand that this appliance requires a break-in period during which small amounts of smoke and curing smells
will be emitted.
Содержание ML54
Страница 2: ...85 03 01145 ML54 HOMEOWNER NOTES...
Страница 16: ...85 03 01145 ML54 Page 16 Figure 4 11 Figure 4 10...
Страница 24: ...85 03 01145 ML54 Page 24 Clearance from Appliance Side Walls Figure 4 18 CLEARANCE TO BODY...
Страница 95: ......
Страница 96: ...Johnson Gas Appliance Company 520 E Avenue NW Cedar Rapids Iowa 52405 Mendota Warranty Registration...