85-03-00944 

38 | 

P a g e

 

 

The following Check-Off Lists must be completed prior to final operation of the Fireplace. 

INSTALLATION CHECK OFF LIST 

 

Co-axial vent rigid pipe, wall vent cap or roof vent cap must be installed by a Mendota 
approved person in accordance with instructions.  All joints must be secured, "twist-
locked" and leak-proof.  1000

º

F sealant must be used on the inner pipe joints of all 

DuraVent pipe sections. 

 

Horizontal or vertical vent cap must be installed "

right-side-up

" and tightly sealed to 

structure per instructions.  Vent Caps must be Mendota approved. 

 

Proper exterior and interior clearances for vent systems and locations for wall vent 
cap/roof vent cap must be maintained. 

 

Carefully check for correct gas pressure, proper size gas lines and for gas leaks. 

 

115 V electrical service and gas supply must be installed in accordance with instructions 
and local and national codes. 

 

LIGHTING CHECK OFF LIST 

 

All items on "Installation Check Off List" (see above) must be completed. 

 

Check for gas leaks and gas pressures prior to installing facing materials. 

 

Install fresh batteries in remote transmitter. Follow “Initializing the System for the first 
time” instructions to synchronize the remote control and the ignition module. 

 

Check air shutter opening - 0" to 1/8" Nat. gas or 1/4” to 1/2” LP gas. 

 

Carefully follow all Lighting and Log Installation Instructions. 

 

Make certain that burners light immediately and flame runs promptly around "curve" in 
rear burner and lights entire burner.  DO NOT proceed with operation unless burner cy-
cles "on/off" without delays. 

 

Make certain that the flame is "stable" and does not "lift" off burner.  If flame lifts off burn-
er, turn unit off and check that all vent pipes are "twist locked" and leak proof, the vent 
cap is "right side up" and that 1000

º

 Sealant has been used on the inner pipe joints of all 

DuraVent pipe sections.  DO NOT proceed with operation if flame is "lifting off" burner. 

Note: Do not separate telescoping sections.  They must be used as complete as-
semblies

 

Make certain glass door is in proper closed position and "centered" in firebox opening. 

 

 

Содержание FV41-ARCH

Страница 1: ...stallation and service must be performed by a qualified installer service agency or the gas suppli er WARNING Do NOT use this appliance if any part has been under water Immediately call a qualified se...

Страница 2: ...t appareil doit tre utilis uniquement avec les types de gas indiqu s sur la plaque signal tique Ne pas l utiliser avec d autres gas sauf si un kitde conversion certifi est install SAFETY AND WARNING I...

Страница 3: ...e agency INSPECT the external vent cap on regular basis to make sure that no debris is interfering with the airflow The flow of combustion and ventilation air not to be obstructed DO NOT abuse the gla...

Страница 4: ...CLEARANCES 16 FRAMING DEPTH FINISHING GUIDES 17 FINISHING MATERIALS INSTALLATION 18 HEARTH PROTECTION PAD REQUIREMENTS 19 BACKUP DC POWER INLET PORT INSTALLATION 20 GAS SUPPLY REQUIREMENTS 21 GAS PRE...

Страница 5: ...ING FOR NORMAL BURNER S IGNITION CHARACTERISTICS 50 FV 41 ARCH VALVE ASSEMBLY REPLACEMENT PARTS 51 FV 41 ARCH GAS IGNITION SYSTEM WIRING DIAGRAM 52 REMOTE CONTROL TRANSMITTER FUNCTIONS 53 REMOTE TRANS...

Страница 6: ...NOT BE PLACED on or near the appliance Children and adults should be ALERTED to the hazards of high surface temperature and should STAY AWAY to avoid burns or clothing ignition Young children should b...

Страница 7: ...State Building Code 3 A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a min imum height of eight 8 feet above grade directly in line with the ex...

Страница 8: ...t least annually by a professional service person More frequent cleaning may be required due to excessive lint from carpeting bedding material carbon build up etc It is imperative that control com par...

Страница 9: ...COMBUSTIBLES 2in 51mm UNIT TO ENCLOSURE BACK WALL 1 2in 13mm VENT PIPE SIDES TO COMBUSTIBLES 1in 25mm UNIT BOTTOM TO ENCLOSURE CEILING 53 1 2 in 136 cm VENT PIPE BOTTOM TO COMBUSTIBLES 1in 25mm UNIT B...

Страница 10: ...nd Mendota approved vent systems and vent caps A non combustible hearth protector with a total insulation rating of R 1 is required when installing this fireplace directly on the floor and must extend...

Страница 11: ...FRONT BURNER AIR SHUTTER CONTROL EXAUST DAMPER ADJUSTMENT FRAMING ATTACH BRACKETS GAS SUPPLY INLET 1 2 M NMP 110 VAC INLET LIFTING HANDLE HEAT TRANSFER DUCTS CONNECTION PORTS 5 X 8 COAXIAL VENT STARTE...

Страница 12: ...red SEE HEARTH PROTECTION PAD R RATING PAGE 12 11 2 HEARTH PAD HEIGHT MIN R 1 RATING IS REQUIRED 45 MIN OPENING WIDTH 51 1 2 MIN UNIT BASE TO 8 MANTEL 8 MANTEL DEPTH AT HEIGHTS SHOWN 72 MIN TO ROOM CE...

Страница 13: ...metal or wood surfaces extending full width and depth of this fireplace An R 1 Rated Hearth Protection Pad 1 1 2 Thick Maximum is required unless this fireplace is elevated For every 1 this fireplace...

Страница 14: ...his fireplace and its vent system Vertical vents that run on the outside of a building may be but are not required to be installed inside a chase Construction of the chase may vary with the type of bu...

Страница 15: ...85 03 00944 15 P a g e CLEARANCES TO COMBUSTIBLES FROM APPLIANCE SURFACES Clearances to Combustibles 0 CLEARANCE FROM TOP STANDOFFS 1 2 CLEARANCE FROM BACK 1 2 CLEARANCE FROM SIDES...

Страница 16: ...hart at right shows the Distance from Fireplace Face the combustible mantel may pro trude outward at a Distance up From Floor Level of this Fireplace If you prefer to take measurements from the Top of...

Страница 17: ...ets Decorative Front Finishing Guides NO FRONT If the Fireplace is installed without a Decorative Front The Fireplace should be finished to the Finishing Guides that come on the Fireplace TRADITIONS F...

Страница 18: ...o the 1 1 2 thickness is towards the control module box Install 1 2 thick drywall on framing members so that its outer surface is flush with the front face of this fireplace Attach Marble or Granite s...

Страница 19: ...he room All hearth pads must be non combustible metal brick stone or mineral fiberboard Do not use any combustible material to pro tect the floor in front of this fireplace For the FV 41 the hearth pr...

Страница 20: ...tch the mounting height of this single gang box with the height of other AC outlets that are installed in the same room as this appliance WARNING DO NOT STAPLE the 6 DC Power Inlet Harness to the wall...

Страница 21: ...less than 1 2 PSIG 3 5 kPa A proper gas line diameter must be selected to run from the supply regulator to the Fireplace Refer to the following table for proper gas pipe diameters Strictly adhere to t...

Страница 22: ...s capacity is not sufficient to add the Gas Fireplace an additional inches to inches regulator must be installed for the Fireplace EXCEPTION Some codes allow 2 PSI 1 4KPA supplies to enter the reside...

Страница 23: ...ading after the 30 minutes of burn time Write the reading here Final Gas Meter Reading _______________ Calculate the following FINAL GAS METER READING INITIAL GAS METER READING Subtract Initial Gas Me...

Страница 24: ...for co axial vent 2 Check to make certain all venting requirements and locations are being followed 3 This Fireplace is designed for installation into rough framing NOTE FRAMING MATERIAL ABOVE FIREPLA...

Страница 25: ...ect Vent Fireplace it is critical that all brands of vent pipe sections are sealed tightly and leak proof This means that all pipe sections must be carefully rotated into the fully twist locked positi...

Страница 26: ...earance to ventilated soffit located above the terminal from the center line of the terminal 24 60 cm min K Clearance to a mechanical air supply inlet 6 feet 1 8 m minimum E Clearance to unventilated...

Страница 27: ...N 1 6 or 7 PIPE DuraVent 6 Amerivent 7 9 12 2 12 VENT STACK 3 24 VENT STACK 4 36 VENT STACK 5 48 VENT STACK 6 90 GALVANIZED ELBOW 45 GALVANIZED ELBOW 7 ADJUSTABLE WALL THIMBLE 8 ATTIC INSULATION SHIEL...

Страница 28: ...aximum Vent System length allowed is 65 feet 4 In Zone A 20 feet maximum horizontal run allowed with a 4 feet starter section If the starter vertical section is less than 4 feet use the chart and redu...

Страница 29: ...ONE A For vent systems that provide a starting vertical section less than 4 feet the following rules apply a You must use the Master Flue Venting Requirements Chart See Zone A below the 4 vertical run...

Страница 30: ...S VERTICAL TERMINATION VERTICAL RISE DUAL 90 ELBOWS HORIZONTAL TERMINATION VERTICAL RISE TRIPLE 90 ELBOWS HORIZONTAL TERMINATION VERTICAL RISE TRIPLE 90 ELBOWS VERTICAL TERMINATION THREE HORIZONTAL DI...

Страница 31: ...l 3 Cut and frame a 10 3 4 wide x 10 3 4 high opening in the wall The hole must be positioned so the vent system will run level or have a rise per foot of run AND be perpendicular to the wall The heig...

Страница 32: ...85 03 00944 32 P a g e 45 1 2 42 1 2 46...

Страница 33: ...ugh any ceilings and will penetrate the outside wall Since vent pipe sections overlap we suggest pre assembling and measuring the total vent pipe run so you can more accurately locate the point where...

Страница 34: ...85 03 00944 34 P a g e...

Страница 35: ...pipe joints DuraVent only are sealed and are leak proof Maintain 1 airspace clearances to combustibles 2 above horizontal runs Cut a 10 x 10 opening in the roof centered in the small drilled hole pla...

Страница 36: ...85 03 00944 36 P a g e FEET MAXIMUM...

Страница 37: ...00 elbows The use of Four 900 elbows must meet some minimum prerequisites Prerequisite 1 The vent system must terminate vertically using a vertical vent cap Prerequisite 2 There must be a minimum 12 i...

Страница 38: ...on Check Off List see above must be completed Check for gas leaks and gas pressures prior to installing facing materials Install fresh batteries in remote transmitter Follow Initializing the System fo...

Страница 39: ...rom unit 4 Door is now free from unit TO REPLACE DOOR 1 Line up the three bottom tabs in glass frame bottom with slots in glass clips on firebox bottom Insert tabs into slots and center tabs in slots...

Страница 40: ...vidual components are available through Johnson Gas Appliance Company Con tact your dealer for more detailed ordering information GLASS FRAME ASSEMBLY HA 78 00103 REPLACEMENT PARTS LIST ITEM PART NUMB...

Страница 41: ...o operate with the blowers turned OFF or ON Turning the blower on increases the overall efficiency of this fireplace and aids in distributing and circulating heat to the room this fireplace is install...

Страница 42: ...ice Person IMPORTANT Try each new shutter setting for approx 1 2 hour before making additional changes NOTE Changes in front burner flame can be made by re arranging the coals as well Densely packed c...

Страница 43: ...ally Exterior glass surface may be cleaned with cleaner as desired To clean interior surface of glass use soap and water CAUTION Do not use oven cleaner to clean glass Clean the glass only when it has...

Страница 44: ...GE 34 C Check condition of glass door gasket gasket must seal tightly over firebox replace if necessary D Periodically check to verify that the vent system and vent cap are open and free of blockage E...

Страница 45: ...ap Orifices drill 54 and Conversion Decal This conversion kit shall be installed by a qualified service agency in accordance with the manufacturer s instructions and all applicable codes and requireme...

Страница 46: ...uctions to access the gas valve 1 Using a Hex Driver remove 4 screws that secure the Log Grate in place Remove Grate from Firebox 2 Remove the Floor Brick Panels by lifting them out of the firebox 3 C...

Страница 47: ...ulator you re moved in Step 2 above The LP Pressure Regulator can only be mounted in one position Secure the LP Pressure Regulator in place Tighten down 5 Remove both Rear and Front Burners Locate and...

Страница 48: ...URE REGULATOR CONVERSION INSTRUCTIONS WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifical ly approved with this appliance may result in prop...

Страница 49: ...h soap and water solution at all plumbing joints prior to placing this appliance into operation It is recom mended that all gas plumbing joints factory installed and field installed are checked for le...

Страница 50: ...h altitude also attach the High Altitude Deration Label supplied in the Owner s Manual Packet to this same surface Prior to attaching the labels fill in all the information that is requested in these...

Страница 51: ...050 SIT Pilot Assembly 4 2 65 14 00042 ORIFICE 42 22 197 BTU NAT 5 1 05 02 00344 885 PROFLAME SIT VALVE 6 1 05 02 00351 Solenoid 885 PROFLAME SPLIT FLOW VALVE 7 1 60 01 00018 NIPPLE 3 8 NPT X 1 5 LONG...

Страница 52: ...res prior to disconnection when servicing controls Wiring errors can cause improper and danger ous operation and Verify proper operation after servicing Attention Au moment de l entretien des commande...

Страница 53: ...ature Press the UP button until the desired temperature is displayed in the SET POINT TEMPERATURE window The fan will turn on 5 minutes after fireplace startup and will turn off 12 1 2 minutes after t...

Страница 54: ...lso extinguish If in Standing Pilot Mode the pilot light will remain ON Note If in SMART model the flame height function is not available for manual adjustment In SMART mode the flame height regulates...

Страница 55: ...eries used the number of ignitions of the appliance the number of changes to the room thermostat set point etc When the Transmitter bat teries are low a Battery Icon will appear on the LCD display of...

Страница 56: ...ce un til the pilot flame lights and the pilot is burning steadily 7 Once the pilot flame is lit and well established close glass door WARNING NEVER IGNITE MAIN BURNERS WITH GLASS DOOR REMOVED OR OPEN...

Страница 57: ...in the CPI Standing Pilot mode to allow the pilot light to remain on indef initely by setting the Remote Transmitter to CPI mode If the remote transmitter is set to the IPI Intermittent Pilot mode the...

Страница 58: ...e FV 41 ARCH LOG SET INSTALLATION INSTRUCTIONS FOLLOW EACH STEP DEPICTED IN THE DIAGRAMS BELOW TO INSTALL THE LOG SET CAUTION LOGS ARE FRAGILE HANDLE LOG PIECES WITH CARE FV 41 ARCH LOG SET PARTS IDE...

Страница 59: ...85 03 00944 59 P a g e...

Страница 60: ...85 03 00944 60 P a g e...

Страница 61: ...85 03 00944 61 P a g e...

Страница 62: ...85 03 00944 62 P a g e...

Страница 63: ...85 03 00944 63 P a g e...

Страница 64: ...85 03 00944 64 P a g e...

Страница 65: ...85 03 00944 65 P a g e...

Страница 66: ...85 03 00944 66 P a g e PLACE SMALL COALS ON TOP OF FLOOR BRICK PANELS AND CLOSE TO GRATE BOTTOM TO SIMULATE A COAL BED...

Страница 67: ...amaged or removed Safety Barrier If the Safety Barrier is damaged contact your Mendota dealer to get a re placement Educate others on the dangers of touching the fireplace Never let children close to...

Страница 68: ...ce can be found on the rating plate which is located inside the right side controls access door When contacting your dealer for any cleaning service or warranty service always provide the Model Number...

Страница 69: ...rizontal and vent runs 1000 sealant must be used on inner joints at adjustable pipe sections CHECK FOR PROPER CLEARANCES TO COMBUSTIBLES VENT LOCATIONS Per Manual INSTALL PROPER SIZE GAS LINES CHECK F...

Страница 70: ...85 03 00944 70 P a g e TAPE SHUT JOHNSON GAS APPLIANCE COMPANY 520 E AVENUE N W CEDAR RAPIDS IA 52405 POSTAGE NEEDED...

Страница 71: ...urchases that have not received prior written approval from Mendota NOTE Minor warping of certain parts or discoloration is normal and is not a defect covered by this warranty Major warping of parts c...

Страница 72: ...85 03 00944 72 P a g e Johnson Gas Appliance Company 520 E Avenue N W Cedar Rapids IA 52405 Mendota Hearth Division WEBPAGE www johnsongas com or www mendotahearth com...

Отзывы: