FRAMING DIMENSIONS
Rough Framing Dimensions
The Rough Framing Dimensions must be main-
tained to allow this fireplace to slide into the fram-
ing cavity with a 90
0
elbow installed on the top
starter collar.
Finished Framing Dimensions
After the FV-41 Fireplace is inserted into the
rough framed cavity, use 2x4’s on each side adja-
cent to the side of this fireplace’s body and on top
of the top framing standoffs to close the air gap
and to act as nailing studs for finishing materials.
Finished framing dimensions are 46.75” x 38.5”.
SPECIAL FRAMING NOTE
: On the left side of this unit, a metal box containing the ignition system protrudes outward.
The front face of this box is located 3-5/8” in from the front face of this unit. For framing depths of 19-1/2 inches, use 2x4s
on the left side with the 3-1/2” dimension of the 2x4 lumber running parallel to the depth of the chase. For framing depths
of 19” (for Granite or Marble facing), run the 3-1/2” dimension of the 2x4 lumber running parallel to the front face of the
unit.
If the fireplace is to be recessed in a cavity deeper than 19-1/2”, all framing and finishing materials protruding past the
front face of this fireplace must be of the NON-COMBUSTIBLE variety.
Constructing the Appliance Chase
A chase is a vertical box-like structure built to enclose this fireplace and its vent system. Vertical vents that run on the
outside of a building may be, but are not required to be, installed inside a chase.
Construction of the chase may vary with the type of building. These instructions are not substitutes for the requirements of
local building codes. Local building codes
MUST
be adhered to.
Chases should be constructed in the manner of all outside walls of the home to prevent cold air drafting problems. The
chase should not break the outside building envelope in any manner.
Wall, ceiling, base plate and cantilever floor of the chase should be insulated. Vapor and air infiltration barriers should be
installed in the chase as per regional codes for the rest of the home. Additionally, in regions where cold air infiltration may
be an issue, the inside surfaces of the chase may be sheet rocked and taped for maximum air tightness.
To further prevent drafts, the fire stops should be caulked with high temperature caulk to seal the gaps. Gas line holes
and other openings should be caulked with high temp caulk or stuffed with unfaced insulation. If the appliance is being
installed on a cement slab, a layer of plywood may be placed underneath this fireplace to prevent conducting cold up into
the room.
Minimum Rough Framing Dimensions
DESCRIPTION DIMENSION
(INCHES)
A Width
45”
B Height
50-1/2”
C
Depth
19-1/2” (19” Granite/Marble Facing)
D
Vent opening height
10-3/4”
E
Vent opening width
10-3/4”
FINALIZED Framing Dimensions
38-1/2"
FINALIZED
WIDTH
46-11/16"
FINALIZED
HEIGHT
19-1/2"
MIN. DEPTH
Содержание FV41-ARCH
Страница 32: ...85 03 00944 32 P a g e 45 1 2 42 1 2 46...
Страница 34: ...85 03 00944 34 P a g e...
Страница 36: ...85 03 00944 36 P a g e FEET MAXIMUM...
Страница 59: ...85 03 00944 59 P a g e...
Страница 60: ...85 03 00944 60 P a g e...
Страница 61: ...85 03 00944 61 P a g e...
Страница 62: ...85 03 00944 62 P a g e...
Страница 63: ...85 03 00944 63 P a g e...
Страница 64: ...85 03 00944 64 P a g e...
Страница 65: ...85 03 00944 65 P a g e...