4. Technician settings (cont’)
- 34 -
P117 – Heat PID Ki (FC only!)
Range: 0...100%
Default: 0%
P118 – Cool PID Kd (FC only!)
Range: 0...100%
Default: 1%
P119 – Heat PID Kd (FC only!)
Range: 0...100%
Default: 1%
P122 – Cool proportional threshold time (update delay) (FC only!)
Range: 0...100 sec.
Default: 60 sec
P123 – Heat proportional threshold time (update delay) (FC only!)
Range: 0...100 sec.
Default: 60 sec
P180 – Show CO
2
readings on the display
0 – Do not show readings on display
1 – Show readings on display
P181 – CO
2
Reading offset
Range: -500…+500 ppm (display shows value divided by 10)
Default: 0 ppm