* For T1,0 functionality – refer to parameter P8 in the technician settings section.
** For IN1,0 functionality – refer to parameter P9 in the technician settings section.
***Communication protocol (MTSC Series only) is set by DIP Switch S1.8 as follows:
S1.8 ON – BACnet
S1.8 OFF – MODBUS
Current ratings:
Outputs 11-16
24/110/230VAC - depending on supply voltage,
3A maximum each
5A total
Outputs AO1, AO2
0-10VDC, 5mA
3. Wiring configuration and DIP Switches
**T2 change over sensor /
T3 Deicing in cool sensor /
Remote OFF switch /
Remote economy switch /
External PIR
11
12
13
14
15
N
L
16
T1
0
IN1
0
*External sensor /
Deicing in cool sensor /
Door switch /
Key-Tag (options)
Main Supply
MTS/MTSC Series:
110/230VAC, 50~60Hz
MTS24/MTSC24 Series:
24VAC, 50~60Hz
AO1
AO2
B
A
See options on
next pages
See options on
next pages
***Communication
(BACnet/MODBUS)
- 13 -
MTSC Series only !