The thermostat continuously monitors the ambient CO
2
level using the
built in CO
2
sensor and compares the readings to the CO
2
set-point.
When the ambient CO
2
level rises above the set-point, the fresh air
damper will open to bring in fresh air.
Additionally, when the ambient CO
2
level exceed the high limit alarm,
an indication will appear on the display.
The values of the CO
2
set-point and high limit alarm, together with
other CO
2
parameters are set by technician.
Please refer to parameters P180-P185 in the technician setting section.
All CO
2
parameters and readings can be monitored through BMS and
optionally trigger other air handling devices to take action.
The CO
2
ambient reading can either be displayed constantly or hidden
by setting either “0” or “1” to technician parameter P180.
Important: Please allow 12 hours of operation from initial power up,
before reading a reliable CO
2
value.
- 9 -
1.12 Fresh air and CO
2
monitoring
Alarms indications may appear on the
top left side of the display as follows:
- CO
2
High limit alarm
- CO
2
High limit + filter alarms
- Filter alarm