3. Wiring configuration and DIP Switches – AC systems
- 14 -
1 2 3 4 5 6 7 8 1 2 3 4 5 6
SW1
SW2
1 2 3 4 5 6 7 8 1 2 3 4 5 6
SW1
SW2
1 2 3 4 5 6 7 8 1 2 3 4 5 6
SW1
SW2
1 2 3 4 5 6 7 8 1 2 3 4 5 6
SW1
SW2
MTSC Series: SW1.8 = Communication Protocol: ON – BACnet, OFF – MODBUS
SW1.4 = HP: ON – Heat pump active in cool, OFF – Heat pump active in heat
HC: ON – Electrical heater, OFF – Oil/Gas heater (no fan)
SW1.5 = ON: Disable compressor delay, OFF – Enable compressor delay
HP
- Heat pump system
HC
- Non heat pump system
##
- Heating/Cooling stages
Fan on/off: 24/110/230VAC, 3A max.
Control - Heat elements, Heat pump, Compressors: 24/110/230VAC, 0.3A max.