B
Pinout
Legend for pinouts:
Note: In the configuration „pulse generator“ (FO) do not forget to
take care of the unused pins DO_8..15. When used as sink drivers
they are in high-impedance state, when used as source drivers
they are connected to ground!
Pin-name
Function
DI_0…15
digital inputs (subdevice 0)
DO_0...15
digital outputs (subdevice 1)
FI_0..7
frequency measurement inputs (alternative configura-
tion)
FO_0...7
pulse generator outputs (alternative configuration)
VCC_EXT
VCC input for ext. power supply of isolated inputs and
outputs, U
ext
typ. 24
VDC
GND_DI
reference ground for isolated inputs (isolated from
outputs and PC ground)
GND_DO
reference ground for isolated outputs (isolated from
inputs and PC ground)