to the terminal will burn MTC.
9.The input and output signal lines connected to MTC shall not be arranged side by side with other
high-power or high-interference lines to reduce interference.
2.2.2 Wiring instructions
User terminal input wiring is shown in Figure 2-4.
Table 2-1 MTC-08-NT enter the user terminal wiring diagram
Figure
①
~
⑦
wiring must be noted that seven aspects:
①
The thermocouple (thermal resistance) signals suggested accessing by shieded compensation cable. Cables away
from power lines or other wires may produce electromagnetic interference. It is recommended to use less than
100 m compensation cable (connecting cable) that be suscepted by noise interference Compensation cable (cable)
exist resistance, will introduce measurement error, adjusting feature to resolve this issue, please refer to the specific
operation "MTC-08-NT thermostat user manual."
②
Thermal resistance (type Pt100, JPt100, Cu100, Cu50) required the three-wire connection.
③
It is recommended to short connect the positive and negative terminals L+ and L- of the channel that is not used, so
as to prevent incorrect data from being detected on this channel.
④
If there is too much electrical interference, connect the shield wire (the shield end of thermocouple compensation
cable, the shield end of thermal resistance connection cable, the shield end of 485 communication wire) to the
temperature controller ground end PG.
⑤
The thermostat grounding PG should be good grounding.
⑥
24V power supply can use the auxiliary output 24Vdc power supply of the main module, or other power supply that
meets the requirements.
⑦
Users need to select the appropriate power supply and solid state relay according to the output mode of 1-4
performance indicators.
2.2.3 Cable specifications
When wiring for MTC-08-NT applications, it is recommended to use multi-ply copper conductors and
prefabricate insulated terminals to ensure the wiring quality. The cross-sectional area and model of the
recommended conductor are shown in table 2-1.
Table 2-1 recommended MTC connection cable wire model