![Megmeet MTC-08-NT Скачать руководство пользователя страница 11](http://html1.mh-extra.com/html/megmeet/mtc-08-nt/mtc-08-nt_user-manual_1765700011.webp)
11
BFM
Content
Remarks
Nat
ure
Sa
ve
CH1/CH5 CH2/CH6 CH3/CH7 CH4/CH8
M8/M12
M9/M13
M10/M14 M11/M15 Auto-tuning setting
of CH1- CH8 *7
Default value
:
0
0:Not self-tuning or aut
o-tuning has been
completed
1
:
Auto-Tune
R/W
Y
#1000/#10
04
#1001/#10
05
#1002/#10
06
#1003/#10
07
Control mode
setting
Default value
:
2
0
:
Hand 1
:
ON/OFF
3:PID
R/W
Y
#1008/#10
12
#1009/#10
13
#1010/#10
14
#1011/#10
15
Heat/cool action*8
Default value
:
1
0:Cooling
1:Heating
2:Heating and cooling
(air cooling)
3:Heating and cooling
(water cooling)
4:Position ratio PID
R/W
Y
#1016/#10
20
#1017/#10
21
#1018/#10
22
#1019/#10
23
Manual output of set
value
Default value
:
0
Range
:
0.0
~
100.0
(%)
R/W
Y
#1024/#10
28
#1025/#10
29
#1026/#10
30
#1027/#10
31
Adjust sensitivity
Setting
(
ON/OFF
control method is
effective
)
Default value:100
Unit
:
0.1
℃
/
℉
Range
:
0~999
R/W
Y
BFM
Content
Remarks
Nat
ure
Sa
ve
CH1/CH5
CH2/CH6 CH3/CH7 CH4/CH8
#1032/#10
36
#1033/#10
37
#1034/#10
38
#1035/#10
39
Auto-tuning
deviation setting
Default value
:
0
Unit
:
0.1
℃
/
℉
Range:
±
input range
R/W Y
#1101/#11
05
#1102/#11
06
#1103/#11
07
#1104/#11
08
Heat side
proportional band
adjusting factor
Default value
:
100%
Setting range:0~1000% R/W Y
#1109/#11
13
#1110/#11
14
#1111/#11
15
#1112/#11
16
Heat side integral
time adjusting factor
Default value
:
100%
Setting range:0~1000% R/W Y
#1117/#11
21
#1118/#11
22
#1119/#11
23
#1120/#12
4
Heat side derivative
time adjusting factor
Default value
:
100%
Setting range:0~1000% R/W Y
#1125/#11
29
#1126/#11
30
#1127/#11
31
#1128/#11
32
Cool side
proportional band
adjusting factor
Default value
:
100%
Setting range:0~1000% R/W Y
#1133/#11
37
#1134/#11
38
#1135/#11
39
#1136/#11
40
Cool side integral
time adjusting factor
Default value
:
100%
Setting range:0~1000% R/W Y
#1141/#11
45
#1142/#11
46
#1143/#11
47
#1144/#11
48
Cool side derivative
time adjusting factor
Default value
:
100%
Setting range:0~1000% R/W Y
#1149/#11
53
#1150/#11
54
#1151/#11
55
#1152/#11
56
Set change rate
limit rise * 10
Default value
:
0
Range:0~range,
Unit
:℃
/second
R/W Y
#1157/#11
61
#11581162 #1159/#11
63
#1160/#11
64
Set change rate
limit drop * 10
Default value
:
0
Range:0~range,
Unit
:℃
/second
R/W Y