21
RECLOSE RELAY Test Screen:
The RECLOSE RELAY Test Screen is used to test reclosing type relays.
The reclosing relay test screen has the same measured values as the
OVERCURRENT
RELAY
test screen, see OVERCURRENT RELAY Test Screen for descriptions. The
primary difference is the number of shots expected before lockout.
RECLOSE SHOT: #
is where the user enters the number of reclose operations that the relay is set for. As
the relay goes through each reclose operation, the appropriate
RECLOSE TIME
is
recorded for each operation. A maximum of 10 reclose operations (shots) may be
recorded.
TIMER RELAY Test Screen:
The TIMER Test Screen is used to do general purpose timing test. For example, when
timing the operating, or trip free operating time of circuit breakers.
The TIMER Start and Stop functions are all described in the TIMER SETUP Screen
described earlier. Note that the time base is also displayed (
60 HZ
or
50 HZ
) to
remind the user what the time base is when timing in Cycles.