results appear on the display screen. Three tactile membrane key switches on the controller are used to
operate the test set. Each key is allocated more than one function during the test procedure, and these
functions are indicated on the display at the relevant point in the programme.

Time Counter (IDMT Testing)
Each test set has a built-in time counter for measuring the time the relay under test takes to operate, or to
reset itself. The relay’s contact-set, is connected to the TIMER STOP terminals allowing the ‘operation’
and/or ‘runback’ times to be measured at the instant the contacts change state. The TIMER STOP inputs
accept either unenergised or 100-264 V a.c./d.c. energised contacts. Note that the PCITS600/2 and
PCITS2000/2 differ from the original versions of the PCITS regarding this feature.

For IDMT testing, the time counter is started when the test current is applied and stopped when the
contacts in the relay under test open or close. The test also stops upon cessation of current (due to load
disconnection) or by manual operation of the hand-held controller. In the ‘runback’ mode, the time counter
starts automatically when the relay contacts operate, or upon cessation of test current, but it must be
stopped using the hand-held controller.

In-built Protection Mechanisms
In-built protection mechanisms include both current overload and thermal protection in the form of circuit
breakers, high breaking capacity fuses and a thermal cut-out.

The current output circuit is protected against overload by two resettable circuit breakers; a short delay
breaker is in series with the variac output and a long delay breaker protects the input circuit. One or both of
these breakers will trip in the event of a significant overload current or fault occurring in the output control
circuit.

For thermal protection, a bi-metallic sensor is mounted in the main transformer which will operate if the duty
cycle is exceeded and an adverse temperature rise in the test set results.

For safety, the circuit has been designed such that when the contacts of the relay under test operate to stop
the time counter, the output of the test set is also switched off. The test set is reset if there is a power
supply failure.

The HBC fuses provide overload protection for the auxiliary output and the controller unit. The solid state
relay which controls the switching on and off of the current output is approved to BASEEFA and ULE86767
standards.

In addition to these protection features of the test sets, a further safety measure is incorporated. If voltage is
detected on the terminals during the setting-up routine, or in the IDMT test-suspension states, then the
variac will automatically wind down to the zero position to ensure that no output is possible and an error
message will be displayed.

Current Setting Capability
The PCITS uses a variac to drive the main output transformer which supplies the required test current. Due
to the variac’s finite winding resolution it is not generally possible to establish a test current that exactly
matches the programmed value. The situation worsens as the load resistance (load plus leads) decreases
since only a small portion of the total variac winding might then be used for setting the required test current.
This can produce a test current which deviates from the programmed value.

To improve the setting accuracy a longer lead set could be used. Additionally the instrument should, if
possible, be used on the high current (low voltage) range to lower the voltage output per winding of the
variac.

The PCITS600/2 normally sets the test current to within 1 A of the programmed value when supplying
higher resistance loads. For the wider range PCITS2000/2 this figure may increase to 3 A. This arises due
to the measurement resolution being 0,2% of the full scale indication.

General Description

6

Содержание PCITS2000/2

Страница 1: ...M PCITS600 2 PCITS2000 2 Primary Current Injection Test Sets User Guide Benutzerhandbuch...

Страница 2: ...ower is switched On The permitted duty cycle must not be exceeded Replacement fuses must be of the correct type and rating The main current terminals must not be connected to a live potential The Test...

Страница 3: ...city 19 Duration Tests 20 Circuit Description 21 Sicherheitshinweise 24 Betriebsanleitung 25 Repair and Warranty 36 Components List 37 Illustrations Figure 1 PCITS 600 2 and PCITS 2000 2 6 Figure 2 Pr...

Страница 4: ...l by which the test set may be separately earthed so that total reliance for earthing is not placed on the supply cable The supply cable must be terminated with a suitable plug bearing in mind the kVA...

Страница 5: ...5 Figure 1 PCITS600 2 and PCITS2000 2...

Страница 6: ...n a bi metallic sensor is mounted in the main transformer which will operate if the duty cycle is exceeded and an adverse temperature rise in the test set results For safety the circuit has been desig...

Страница 7: ...ry testing usually requires a high current over 500 A Secondary current injection testing is easier since there is not the need to break the primary circuit and the current required through the operat...

Страница 8: ...Operation 900 RH at 40 C for 48 hours Storage 93 RH at 40 C for 12 hours SupplyVoltage 220 V 240 V 6 10 50 Hz 60 Hz single phase i e 198 V to 254 V at full output current 7 kVA for PCITS2000 2 3 5 kV...

Страница 9: ...ance lead set 3 m long 6220 462 600 A low inductance lead set 5 m long 6220 463 Duty cycle on test leads 21 2 minutes on and 15 minutes off Trolley for PCITS600 2 6320 224 Leads for timer stop and aux...

Страница 10: ...oltage is used and that the supply cable is terminated by a suitable plug The supply capacity must be sufficient to maintain the supply voltage within range at the full output of the test set 9 Use a...

Страница 11: ...is Note This message occurs frequently during the testing procedure but remains only for a short time while the variac returns to zero and the circuit makes itself ready to continue When the test set...

Страница 12: ...extreme temperatures the display might need altering to obtain visibility The following procedure can be used for recovering normal display contrast a Using the POWER switch turn the test set off and...

Страница 13: ...to the set level It will remain at that level until the OFF key is pressed this choice leads back to the current testing option screen To increase or decrease the test current during the test use the...

Страница 14: ...e option to REPEAT the test or ESCAPE to the current test sub menu figure 5 Operation 14 Return to the current testing option screen Use arrow keys to increase or decrease the SET CURRENT Output being...

Страница 15: ...back time is then given with the option to REPEAT the test or ESCAPE to the current test sub menu figure 5 15 Return to the current testing option screen Use arrow keys to increase or decrease the SET...

Страница 16: ...ith the option to REPEAT the test or ESCAPE to the current test sub menu figure 5 Operation 16 Return to the current testing option screen Use arrow keys to increase or decrease the SET CURRENT Output...

Страница 17: ...lost 2 Manual testing From the AUX VOLTS testing options screen press MANUAL Pressing START automatically begins a test and causes the voltage to rise to the set level It will remain at that level unt...

Страница 18: ...t ranges the warning is cleared if the test current is corrected in the allowed time However the indication remains for the duration of an IDMT test and the subsequent results screen This warns the op...

Страница 19: ...h less significant To give some guidance regarding the performance of various cross sections and lengths of cables figure 7a is provided With the leads strapped together the Foster PCITS2000 2 will de...

Страница 20: ...C ambient Recovery time after a full duration test is 15 minutes operation is continuous at approximately 40 of full power Operation 20 200 0 10 2 5 20 30 40 50 400 600 800 1 000 1 200 1 400 1 600 1 8...

Страница 21: ...ither series or parallel primary connections to change the output range of the test set It has an extra pole which is used to send a signal to the microprocessor so that the correct range can be indic...

Страница 22: ...ransformer combination A phased turn off prevents residual magnetization of the loading transformer and ensures proper re energisation These features significantly reduce nuisance effects caused by pr...

Страница 23: ...23...

Страница 24: ...r t nicht ber hrt werden Die zul ssige Betriebsdauer darf nicht berschritten werden Beim Austausch von Sicherungen mu die richtige Klasse und Sorte verwendet werden Die Netzstromanschl sse d rfen nich...

Страница 25: ...n Stecker versehen ist Die Netzstromkapazit t mu ausreichend sein um die Netzstromspannung innerhalb des Bereiches der vollen Leistung des Pr fger tes zu halten 9 Nur Netzsteckdosen mit Schutzerdung v...

Страница 26: ...erscheint beim Pr fen mehrmals f r kurze Zeit wenn sich der Variac auf Null stellt und der Stromkreis zum Fortsetzen der Pr fung vorbereitet wird Beim Einschalten des Pr fger tes vollzieht der Schrit...

Страница 27: ...ungen benutzt oder aufbewahrt wird m ssen die Bildschirmeinstellungen evtl ver ndert werden um ein Ablesen der Werte zu erm glichen Der normale Bildschirmkontrast l t sich wieder wie folgt einstellen...

Страница 28: ...ART wird die Pr fung automatisch begonnen und der Strom bis zum eingestellten Stand erh ht Dieser Stand wird beibehalten bis die Taste EIN gedr ckt wird womit zum Strompr fungs Optionsbildschirm zur c...

Страница 29: ...fung a Vorw rtspr fung W hlen Sie im Pr foptionsbildschirm STROM zun chst RELAIS und anschlie end VORL Die Betriebszeit wird auf dem Bildschirm dargestellt Die Pr fung wird unter einer der folgenden...

Страница 30: ...kte iii Dr cken der START R CKLAUF Taste oder iv nach 600 Sekunden mit laufendem Strom Der R cklaufzeitschalter wird durch Dr cken der STOP Taste angehalten oder stellt sich nach 600 Sekunden automati...

Страница 31: ...des Stroms ii Bet tigung der Relaiskontakte iii Dr cken der START R CKLAUF Taste oder iv nach 600 Sekunden mit laufendem Strom Der R cklaufzeitschalter wird durch Dr cken der STOP Taste angehalten ode...

Страница 32: ...NDERT BITTE WARTEN vorprogrammierte Pr fdaten sind dann m glicherweise verlorengegangen 2 Manuelle berpr fung Dr cken Sie im Pr foptionen Bildschirm HILFSSPANNUNG auf MANUEL Wenn Sie auf DR CKEN wird...

Страница 33: ...innerhalb der vorgegebenen Zeit korrigiert wird Bei einer IDMT Pr fung wird das Ausrufezeichen jedoch w hrend der Testdauer und auf dem folgenden Ergebnisbildschirm weiterhin angezeigt um den Bediener...

Страница 34: ...sultierende Induktanz spielt eine weitaus geringere Rolle In Abbildung 7a werden die Eigenschaften verschiedener Kabell ngen und querschnitte dargestellt Bei zusammengebundenen Kabeln liefert Foster P...

Страница 35: ...Pr fung bei einer bestimmten Ausgangsstromst rke und einer Umgebungstemperatur von 20 C dargestellt Die Erholungszeit nach einer vollen Testl nge betr gt 15 Minuten ein kontinuierlicher Betrieb ist be...

Страница 36: ...Archcliffe Road Valley Forge Corporation Center Dover 2621 Van Buren Avenuel Kent CT17 9EN Norristown PA 19403 England USA Tel 44 0 1304 502243 Tel 610 676 8579 Fax 44 0 1304 207342 Fax 610 676 8625...

Страница 37: ...37...

Страница 38: ...38...

Страница 39: ...APPES France T 33 1 30 16 08 90 F 33 1 34 61 23 77 OTHER TECHNICAL SALES OFFICES Toronto CANADA Sydney AUSTRALIA Madrid SPAIN Mumbai INDIA and the Kingdom of BAHRAIN Megger products are distributed in...

Отзывы: