PAT400 Series
88
Differential leakage current
■
■
■
Test voltage & frequency:
Nominal mains supply
■
■
■
Differential leakage current accuracy:
±5% ±5 digits
■
■
■
Differential leakage current resolution:
0.01 mA
■
■
■
Display range:
0.00 to 19.99 mA
■
■
■
Reading corrected to nominal supply v10%
■
■
■
Touch current test
■
■
■
Test voltage & frequency:
Nominal mains supply
■
■
■
Touch current accuracy:
±5% ±5 digits
■
■
■
Touch current resolution:
0.01 mA
■
■
■
Display range:
0.00 to 10 mA
■
■
■
Reading corrected to nominal supply v10%
■
■
■
Operational test
■
■
■
Test voltage & frequency:
Nominal mains supply
■
■
■
VA Accuracy:
±5% ±10 digits (0 to 99 VA)
±5% ±50 digits (100 VA - 999 VA)
±5% ±100 digits (1000 VA - 3700 VA)
■
■
■
■
■
■
■
■
■
Resolution:
1 VA (0 to 3700 VA)
■
■
■
Display range:
0.00 to 3.99 KVA
■
■
■
Reading corrected to nominal supply voltage
■
■
■
Extension lead test
■
■
■
Tests performed:
Bond, Insulation & Polarity
■
■
■
Polarity test voltage:
12 V dc
■
■
■
Polarity checks:
Lead OK
Live neutral S/C
Live neutral reversed
Live/neutral O/C
■
■
■
■
■
■
■
■
■
■
■
■
Flash test
■
Flash test voltage:
1500 V a.c nominal for Class 1
■
3000 V a.c nominal for Class 2
■
Flash test current:
< 3.5 mA short circuit @ 253 V primary supply voltage
■
Flash test breakdown current accuracy:
±5% ±5 digits
■
Flash test breakdown current resolution:
0.01 mA
■
Display range:
0.00 to 3.0 mA
■
Portable RCD test
■
■
■
Test voltage & frequency:
Nominal mains supply
■
■
■
Test current accuracy:
-8% to –2% (1⁄2 ⁄ x I)
+2% to +8% (1 x I, 5 x I)
■
■
■
■
■
■
Trip time accuracy:
±1% ±5 digits
■
■
■
Trip time resolution:
0.1 ms
■
■
■
Display range:
0 to 1999 ms (1⁄2 ⁄ x I)
0 to 300 ms (1 x I)
0 to 40 ms (5 x I)
■
■
■
■
■
■
■
■
■