20
PREVENTIVE MAINTENANCE
TECHNICAL SPECIFICATION
Clean only with a damp cloth. Do not use any alcohol based cleaning fluids
as they may leave a residue.
General Specification
Only values with tolerances or limits are guaranteed data. Values without
tolerances are for information only.
Voltage measurement
Range:
0 V to 500 V
Accuracy:
±2% ±2 digits
Frequency measurement (LT320 and LT330)
Range:
25Hz to 450Hz
Accuracy:
25.0Hz to 199.9Hz ±0.1Hz
200Hz to 450Hz ±1Hz
Phase rotation indicator (LT320 and LT330)
Three wire identification of phase rotation.
Loop ranges (to EN 61557-3)
3-wire No Trip Loop (Line to Earth)
Supply
(LT310)
100 V - 280 V 45Hz to 65Hz
(LT320 and LT330)
50 V - 280 V 45Hz to 65Hz
Nominal test current:
15mA line to earth
Loop accuracy
0.01
Ω
- 9.99
Ω
(±5% ±0.03
Ω
)
10.0
Ω
- 99.9
Ω
(±5% ±0.5
Ω
)
100
Ω
- 999
Ω
(±5% ±5
Ω
)
1.00 k
Ω
- 2.00 k
Ω
(±5% ±30
Ω
)
Содержание LT310