(Hold the key down to scroll quickly through the numbers)

3.  Select distribution board number (b01,02 etc) using 

↑↓

keys 

then press NEXT

4.  Select circuit number (c01,02 etc) using 

↑↓

keys then press NEXT

5.  Select L-L, L-E, L-N etc by pressing the 

↑↓

keys, then press NEXT

6.  Select the Phase using 

↑↓

keys then press NEXT.  The screen 

will display a unique test number, which is attached to that  particular 

test. 

7. Press OK to save the result.

To store a subsequent result:

To save the next test under the same location job number, distribution

board etc:

1. Make another measurement as described earlier and press STORE.

2. The last Job number  will be displayed. Press OK.

3. The unique test number will be displayed. Press OK and the result is 

stored.

Note:

To change any setting before saving a result, scroll down through

the result using the NEXT/LAST keys. Change the reference number using

the 

↑↓

keys and press OK.

To recall the last test result:

1. Set the range knob to RCL

2.  The last unique test number is displayed

3.  Press OK and the test result will be displayed.

Note:

Only the last test result can be recalled to the display.

To recall the PFC value press LAST or NEXT value if applicable.

17

TEST RESULT STORAGE (LT330 ONLY)

Storing LOOP test results:

Results storage has the following structure:

000,  

001…255

= Job number

b00, b01, b02 …99

= Distribution board No.

c00, c01, c02…99

= Circuit number

R12, RrN,Rr2,Rr1,R1& R2 

= Circuit type

P1 to P3 

= Phase

000, 

001…… job number acts as work folders. Sets of results

can be saved to a particular job number and easily separated when
downloaded.

b01, b02…  distribution board number:

c01, c02…  circuit reference 

Results can be assigned a specific distribution board number and circuit

reference number.

L-E, L-N… -  circuit type:  allows a test to be defined as the circuit type.

P1,P2,P3   Phase number:  Each test can be stored under a particular

phase, P1, P2 or P3.

Unique test number:  Each test result is assigned a unique test number,

from 0 to 1999 logged automatically. This cannot be changed by the user.

To store a result:

1. Make a Z, MaxZ, Zref or R1+R2 loop measurement as descried 

earlier and Press STORE.

2.  Select Job reference number using 

↑↓

keys then press NEXT.

Содержание LT310

Страница 1: ...M LT300 Series Earth Loop Testers USER MANUAL...

Страница 2: ...orities may recommend the use of fused test leads when measuring voltage on high energy systems The battery cover must be in place whilst conducting tests Voltage indicator LED s cannot reveal a N PE...

Страница 3: ...warnings 3 Introduction 4 General description 5 Case contents 7 LCD display 6 Front panel 6 Connection panel 7 Lid open closure 7 Preparations for use 8 Batteries 8 Preliminary test lead check 8 Gener...

Страница 4: ...test Phase Phase loop test PFC display INTRODUCTION GENERAL DESCRIPTION 4 Thank you for purchasing the Megger Earth Loop Impedance Tester For your own safety and to get the maximum benefit from your...

Страница 5: ...s 1 x Plug ended test lead 8 x AA LR6 batteries fitted in instrument 1 x Warranty card 1 x Certificate of test 1 x Calibration certificate 1 x CD containing user manual 1 x Quick start guide 1 x Downl...

Страница 6: ...6 LCD DISPLAY FRONT PANEL...

Страница 7: ...any time OK Final operation to save the result Selects the job db circuit number ie 01 02 03 etc Lid open closure 1 Open lid by lifting up front panel tab 1 2 Fold away underneath instrument 2 3 and p...

Страница 8: ...strument will warn the operator and prevent further testing until the instrument has had a chance to cool down Fuse Blown A fuse blown will prevent the instrument from making further tests The fuse in...

Страница 9: ...hot Indicates the instrument needs to cool down before it can continue loop testing Noise on the circuit under test may affect the reading Setup procedure Reverse polarity or line neutral swapping Thi...

Страница 10: ...appliance The mains plug test lead supplied with the Megger tester is a test lead that forms part of the measuring circuit of the instrument The overall length of this lead must not be altered If the...

Страница 11: ...ipping loop test No Trip Earth loop impedance measurement at a power socket The No Trip range is a high resolution 0 01 low test current earth loop resistance measurement range It requires a connectio...

Страница 12: ...ssing the TEST button 12 Bonded metalwork testing Repeat the above test but with the green lead connected to the exposed metalwork For a Hi current phase to earth loop impedance measurement at a power...

Страница 13: ...display will show 480 V Over temperature hot To protect the instrument from over heating during Loop testing thermal protection is fitted If the message hot appears in the display together with the G...

Страница 14: ...d result must be stored in the instrument s memory Zref prior to measuring R1 R2 Saving a Zref distribution result 1 Switch the range knob to Zref 2 Select a No Trip or Hi loop test as appropriate 3 C...

Страница 15: ...the phase to earth voltage Phase to Phase voltage measurement LT320 and LT330 NOTE measured voltage must not exceed 300 V phase to earth To measure the voltage of the electrical supply 1 Set the inst...

Страница 16: ...show the phase sequence indicates R B Y sequence or 1 2 3 indicates R Y B sequence or 1 3 2 NOTE If one of the lines is faulty neither of the symbols is displayed and just the normal neon polarity ind...

Страница 17: ...r is displayed 3 Press OK and the test result will be displayed Note Only the last test result can be recalled to the display To recall the PFC value press LAST or NEXT value if applicable 17 TEST RES...

Страница 18: ...NING This operation is not reversible All data will be deleted 18 REPLACING BATTERIES Batteries Battery type 8 x LR6 AA 1 5 V Alkaline or 8 x 1 2V NiCAD or 8 x 1 2V NiMH Low battery warning symbol The...

Страница 19: ...tended periods of time Fuse Blown indication The fuse blown symbol findicates that an internal fuse has failed This instrument is fitted with a factory fitted fuse and should only be replaced by an au...

Страница 20: ...rement Range 0 V to 500 V Accuracy 2 2 digits Frequency measurement LT320 and LT330 Range 25Hz to 450Hz Accuracy 25 0Hz to 199 9Hz 0 1Hz 200Hz to 450Hz 1Hz Phase rotation indicator LT320 and LT330 Thr...

Страница 21: ...idity Operating range 5 C to 40 C Operating humidity 93 R H at 40 C max Storage range 25 C to 70 C Maximum altitude 2000 m Environmental protection Weather proof to IP54 Safety Meets the requirements...

Страница 22: ...ng amendment No 1 Basic and service errors Loop test ranges The basic error is the maximum inaccuracy of the instrument under ideal conditions whereas the service error is the maximum inaccuracy takin...

Страница 23: ...plug test lead BS 1363 BS Versions 6220 740 Mains plug test lead CEE 7 7 EN versions 6220 741 Mains plug test lead AS NZS 3112 AU versions 6220 790 USB download lead 25970 041 Download Manager CD 6111...

Страница 24: ...ng and Instrument for Repair If it is necessary to retun an instrument for repair a Returns Authorisation number must first be obtained by contacting one of the addresses shown You will be asked to pr...

Страница 25: ...er com Megger Pty Limited Unit 26 9 Hudson Avenue Castle Hill Sydney NSW 2125 Australia T 61 0 2 9659 2005 F 61 0 2 9659 2201 E ausales megger com Megger Limited 110 Milner Avenue Unit 1 Scarborough O...

Отзывы: