c.
RCD / GFCI personal protection test result
The EVCC300 will apply pre-set test limits depending on the set mains supply and the test performed. There are three
conditions that can be indicated to the user.
(
) Green tick – PASS
(
) Orange tick – Questionable
(
X
) Red cross – FAIL
A PASS result will indicate as follows:
The orange, questionable result indicates that, although the trip time was fast enough to meet the requirements of
a standard, it wasn’t as fast as many manufacturers might recommend. In this situation it is recommended that a
qualified electrician is consulted.
Note:
Questionable test results will only occur when the EVCC300 is set to a US mains supply voltage.
Should a red FAIL result occur the charger should be taken out of use until a new RCD / GFCI can be fitted.
23
Tests
www.calcert.com
1.800.544.2843
0
5
10
15
20
25
30