5.3.2 How to perform the test
1. Switch the instrument ON.
2. Connect the black ground / earth continuity test lead to
the 4 mm socket at the bottom of the instruments handle.
3. Plug the EVCC300 into the charger outlet, either directly into
a type 2 connector or using the adaptor provided into a type
1 connector.
Ensure the connection method indicated in the top left corner of
the MENU screen is correct.
As a reminder the menu screen connection indicator looks like
this.
In this screen the EVCC300 is set to direct connection. If the red
cross is not present the instrument is set for connection to the
charger via a tethered cable or plug in charging cable.
4. Use the softkeys 1 and 3 to select the R
PE
test indicated
in orange.
5. Press softkey 2 to SELECT test.