RCD / GFCI nuisance trip test result
The EVCC300 will apply pre-set test limits depending on the set mains supply and the test performed. There are three
conditions that can be indicated to the user:
(
) Green tick – PASS
(
) Orange tick – Questionable
(
X
) Red cross – FAIL
A PASS result will indicate as follows:
The orange, questionable result indicates that, although the trip current was of a reasonable level, it may be of a level
being influenced by additional leakage or due to a over sensitive device. In this situation it is recommended that a
qualified electrician is consulted.
Should a red FAIL result occur the charger the trip level is of concern and will most likely result in nuisance tripping of
the RCD or GFCI is use. A qualified electrician should be consulted.
d.
The criteria for the result indication is as follows:
230 V Ph to N (UK / Europe tests)
AC current ramp test
PASS / FAIL criteria:
FAIL:
(
X
)
RCD trips between 2 mA to 14 mA
QUESTIONABLE:
(
)
RCD trips between 16 mA to 24 mA
PASS:
(
)
RCD trips between 26 mA and 30 mA
FAIL:
(
X
)
No RCD trip in 4.5 seconds
DC current ramp test
PASS / FAIL criteria:
PASS:
(
)
No RCD trip
FAIL:
(
X
)
RCD trip