AVTM246004 BITE 2/2P Rev 4 July 2011
62
•
temperature
•
state of charge
•
load conditions
These conditions should be monitored and recorded before
making measurements. A large difference in the impedance of
an individual or group of cells indicates a potential problem
and warrants additional investigation.
Instantaneous Interpretation
The BITE 2/2P
receiver
has the ability to calculate
impedance variations based on a preset baseline or
benchmark value. On start-up (or after wanding) the
following screen will appear:
Y
ENTER BASELINE?
N
(Y/N)
MENU
To enter a baseline or benchmark value, press
to display
the following screen:
BASE
WARN
FAIL
XX.XX
XX%
XX%
Enter the value by using
to enter 0-9 or decimal point.
Use
to move to the next place.
To set the “Warning” level, enter a percent change using the
same technique. The default warning value is 20% variation.
The screen will display:
BASE
WARN
FAIL
20.25
25%
XX%
Continue to the “Fail” level and follow the same steps. The
default fail value is 40% variation.