M
AVTM246004 BITE 2/2P Rev 4 July 2011
50
B
Not to
exceed
250 V dc
J2
From transmitter
(current source
leads)
A
Figure 5-2: Sectioning a battery system greater than 275 V
The potential between the
current source leads
(red at A
and black B) in Figure 5-1 cannot exceed 275 V. To section
the string:
1.
Place the
current source leads
(at points A and B) in the
string so that the potential does not exceed 275 V.
2.
Test the cells located between connections A and B.
3.
When you are finished testing the cells, press the Current
switch on the
transmitter
to the
O
(OFF) position.
NOTE:
If you have to move the transmitter to test the next
section, you may need to power down and disconnect the
transmitter. (See "Powering Down and Disconnecting the BITE
2/2P" on page 45.)
4.
Remove the
current source leads
from the battery. Then
move them to the next section to be tested (not to exceed
275 V).
www.
GlobalTestSupply
.com
Find Quality Products Online at: