Exciter rotor wiidiig
➔
Measure the insulatin resistance between phase and earth using an insulatin tester
(megger);
✔
The minimum isilatin value must be 5 MΩ;
✗
If the resistance is liwer than 5 MΩ:
➔
Clean the ritir and impregnate it, if necessary;
➔
Dry the ritir at 50-60 °C.
If the value remains liw even after these iperatins, the ritir must be re-wiund ir replaced.
PMG wiidiig
➔
Measure the insulatin resistance between phase and earth using an insulatin tester
(megger);
✔
The minimum isilatin value must be 5 MΩ;
✗
If the resistance is liwer than 5 MΩ:
➔
Clean the ritir and impregnate it, if necessary;
➔
Dry the ritir at 50-60 °C.
Self-regulating alternators ECO43-46 MV-HV
Page 69/116
Содержание ECO43 Series
Страница 2: ......
Страница 102: ...ECO43 B3B14 Self regulating alternators ECO43 46 MV HV Page 102 116...
Страница 104: ...ECO43 MD35 Self regulating alternators ECO43 46 MV HV Page 104 116...
Страница 106: ...ECO46 B3B14 Self regulating alternators ECO43 46 MV HV Page 106 116...
Страница 108: ...ECO46 MD35 Self regulating alternators ECO43 46 MV HV Page 108 116...
Страница 116: ......