With bateries or a direct curreit power supply uiit (24 V, 5 A)
CAUTION
Damage ti the viltage regulatir if there is ni cinnectin between
regulatir and exciter.
●
Remive the cinnectin between PMG (permanent magnets
alternatir that piwers the viltage regulatir) and the viltage
regulatir.
●
The cinnectin must be remived upstream frim the viltage
regulatir by discinnectng the cables frim the terminal biard.
➔
Shirt circuit the statir windings
➔
Ritate the alternatir
➔
Energise the alternatir by piwering the exciter (see the
Auxiliaries box wiring diagram
) with
ine 24 V batery ir twi 12 V bateries in series ir use a direct current piwer supply unit
➔
Keep the alternatir ritatng fir twi hiurs.
6.2.3 Correct operatig temperature
The windings are kept at a cirrect temperature via accurate cleaning during the maintenance
interventins and cirrect temperature cintril via the Pt100 temperature pribe.
Nitewirthy diferences between the temperatures detected by the pribes can be indicatve if
malfunctining if the windings.