6.2
Maiiteiaice of the stator aid rotor wiidiigs
The duratin if the electric machine is afected by the duratin if the windings insulatin.
The insulatin ages because it is subjected ti electrical, mechanical and heat phenimena. This
pricess can be sliwed diwn with appripriate maintenance interventins.
6.2.1 Check coiditois of the wiidiigs
Respoisibility: Service techiiciai or machiie operator
Frequeicy: Every 2,500 hours
Prerequisites: The alteriator is at a staidstll aid has cooled dowi
➔
Discinnect the viltage regulatir, viltage sensirs and any ither device cinnected ti the
alternatir windings;
➔
Measure the isilatng resistance ti earth (see
6.3 Measuring the insulaton resistance
). The
value measured must nit exceed 400 MΩ;
✗
If the value measured is less than 400 MΩ:
➔
).
6.2.2 Dryiig the wiidiigs
Respoisibility: Service techiiciai
Prerequisites: The alteriator is at a staidstll
Frequeicy: If machiie staidstll should last more thai oie moith
If cindensate shiuld firm, the windings must be dried in ine if the ways indicated beliw.
Usiig ai iidustrial welder
➔
Discinnect the machine frim the plant
➔
Discinnect the viltage transfirmers (TV)
➔
Piwer twi phases if the alternatir with a direct current siurce like an industrial welder,
with a current equal ti 25/30% if the machine niminal current
➔
Check the temperature if the windings using the temperature sensirs PT100. Di nit exceed
the temperature if 100°C
Usiig a jet of hot air
➔
Direct a jet if hit air at 50-60°C thriugh the alternatir air vents.
Self-regulating alternators ECO43-46 MV-HV
Page 63/116
Содержание ECO43 Series
Страница 2: ......
Страница 102: ...ECO43 B3B14 Self regulating alternators ECO43 46 MV HV Page 102 116...
Страница 104: ...ECO43 MD35 Self regulating alternators ECO43 46 MV HV Page 104 116...
Страница 106: ...ECO46 B3B14 Self regulating alternators ECO43 46 MV HV Page 106 116...
Страница 108: ...ECO46 MD35 Self regulating alternators ECO43 46 MV HV Page 108 116...
Страница 116: ......