4.5.2.6 Basic function
–
Send value
Single-button function
The following figure shows the available settings:
Figure 31: Settings
–
Single-button function: Send value
Each time the button is pressed, the set value is always sent, either as a percentage, decimal value or
scene.
The following table shows the available settings:
ETS-Text
Dynamic range
[Default value]
Comment
Datapoint type
▪
1Byte DPT 5.005
Decimal factor (0…255)
▪
1Byte DPT 5.001 Percent (0…100%)
▪
1Byte DPT 17.001 Scene number
Setting the datapoint type for
the value to be sent.
Table 40: Settings
–
Single-button function: Send value
The value to be sent can be set according to the set datapoint type.
The values that can be set are 0 -
100%
(percentage value),
0
- 255 (value) or
1
- 64 (scene).
The following table shows the available communication object:
Number
Name/Object Function
Length
Usage
131
Button left
–
Send percent value,
send value, send scene
1 Byte
Sending the value.
DPT depending on the parameter setting
Table 41: Communication objects
–
Single-button function: Send value