Technical Manual
Motion Detector/Automatic Switch 55/63
Series .02
MDT technologies GmbH •
51766 Engelskirchen • Papiermühle 1
Tel.: +49-2263-
880 • Fax: +49-2263-4588 • [email protected] • www.mdt.de
16
16
The following table shows the possible settings:
ETS-Text
Dynamic range
[Default value]
Comment
Active sensors
•
--
•
1-
•
-2
•
12
Setting which sensors are active for this
channel.
Information about
sensor assignment
Position of sensors
If the mark is set by clicking on the
checkbox, a sketch appears with
information about the positions of the
sensors S1 and S2.
Sensitivity
•
basic setting
(General settings)
•
individual
Selection of whether the values for the
sensitivity from the "General settings"
menu are used or whether they are set
individually for the light channel.
Individual: Sensitivity 0 (lowest level)
only possible from DB V4.4 and from
device HW R2.5.
Brightness
•
basic setting or object
„Dark switch“ active
•
Independent of
brightness
Basic setting or object „Dark switch“
active:
The light channel uses the
brightness settings of the “General
settings” but can be switched
brightness-independently with a "1" to
the "Switch dark" object.
Independent of brightness:
The light
channel switches independently of the
measured brightness.
Channel mode
•
fully automatic
•
half automatic (manual
switching)
Setting whether the device operates as
a fully automatic or semi-automatic
device
Motion filter in standby
•
not active, no filtering
•
active, filter short
motions
Activation of a motion filter in readiness
(= output is switched off).
Only in fully automatic operating
mode
!
Reduction of follow-up
time
•
not active
•
active
Setting whether a shortening of the
follow-up time is to be activated
Maximum duration for
short time presence
10 s,
20 s
, 30 s,
Setting the maximum duration for a
short-time presence
Follow-up time for
short time presence
10 s, 20 s,
30 s
, 45 s, 60 s, 90 s,
120 s
Setting the follow-up time for the short-
time presence
Follow-up time
“
Day
”
1 s
–
4 h
[3 min]
Setting the follow-up time for Day mode
Follow-up time
“
Night
”
1 s
–
4 h
[30 s]
Setting the follow-up time for Night
mode
Table 6: Basic settings
–
Light channel