Table 13: Belt deflection force
Front Load Filter Option
Front loaded filter options require that the filters be removed
and replaced from inside the unit.
To remove filters, rotate the wire clips. This will release both
the pre-filter and the final filter. When installing clean fil-
ters, check to verify the filters are fully seated in the frame.
See Figure 30.
Figure 30. Frame and filters with holding clips
CROSS SECTION
SHEAVE DIAMETER (INCHES)
DEFLECTION FORCE (LBS.)
SMALLEST SHEAVE
DIAMETER RANGE
RPM RANGE
BELT DEFLECTION FORCE
CROSS SECTION A, B, 5V
CROSS SECTION AX, BX, 5VX
USED BELT
NEW BELT
USED BELT
NEW BELT
A, AX
3.0-3.6
1000-2500
3.7
5.5
4.1
6.1
2501-4000
2.8
4.2
3.4
5.0
3.8-4.8
1000-2500
4.5
6.8
5.0
7.4
2501-4000
3.8
5.7
4.3
6.4
5.0-7.0
1000-2500
5.4
8.0
5.7
9.4
2501-4000
4.7
7.0
5.1
7.6
B, BX
3.4-4.2
850-2500
4.9
7.2
2501-4000
4.2
6.2
4.4-5.6
860-2500
5.3
7.9
7.1
10.5
2501-4000
4.5
6.7
7.1
9.1
5.8-8.6
860-2500
6.3
9.4
8.5
12.6
2501-4000
6.0
8.9
7.3
10.9
5V, 5VX
4.4-6.7
500-1749
10.2
15.2
1750-3000
8.8
13.2
3001-4000
5.6
8.5
7.1-10.9
500-1740
12.7
18.9
14.8
22.1
1741-3000
11.2
16.7
13.7
20.1
11.8-16.0
500-1740
15.5
23.4
17.1
25.5
1741-3000
14.6
21.8
16.8
25.0
WARNING
Moving belt and fan can cause severe personal injury or
death. During installation and filter maintenance:
1. Verify that the belt and fan guards on plenum fan units are
always in place.
2. Lock and tag out fans to prevent accidental start up.
3. Do not enter the filter compartment until the fan is completely
stopped.
4. Use approved equipment for reaching filters located above nor-
mal reach. Do not step on filter frames or unit components.
5. Floor surfaces must be dry and free of oil or grease.
AVERTISSEMENT
Pendant l'installation et où l'entretien des filtres, une cour-
roie en mouvement ou un ventilateur en opération peuvent
causer des blessures graves où même causer la mort.
1. S' assurer que les gardes de courroie et de ventilateur sont tou-
jours en place.
2. Verouiller les démarreurs des ventilateurs et afficher un avis de
mise-en-garde afin de prévenir tout accident ou démarrage.
3. Attendre que le ventilateur soit complètement arrêté avant d'
entrer dans l' unité.
4. Utiliser seulement des équipements approuvé pour joindre les
bancs de filtres; ne pas mettre soit sur les cadres des filtres ou
même sur toutes composantes de l'unité.
5. La surface des planchers doit être sec et libre de toute trace
d'huile et où de graisse.