FIGURE 13 Continued. TROUBLESHOOTING GUIDE

COMPRESSOR STARTER
OVERLOAD TRIPPED

HUNTING

COMPRESSOR
WILL NOT LOAD

COMPRESSOR
WILL NOT UNLOAD

CANNOT RESET
CONTROL CIRCUIT

MOTOR

 

PRESS 

1. Motor circuit problem.

2. Overload relay calibration.

3. Current limit  set too high

in control module.

4. Faulty current transformer (C.T.).

5. Single phase.

1 Capacity control vane speed.

2. Fast pulse rate (control module).

3 Faulty expansion valves

4. Fluctuating evaporator water flow.

5. Low refrigerant charge

6. Low condenser water temperature

1. Faulty control module

2. Shorted sensor circuit (chiller)

3. Open sensor circuit  (Templifier).

4. Wrong module jumper con-

nections.

5. Defective SB solenoid coil

6. Loss of CT voltage.

7. SB needle valve closed/

restricted.

8. Faulty relay R4.

9. Low refrigerant charge.

10. Vane seal leakage.

11. Faulty LPO switch.

1. Open sensor (chiller)

2. Shorted sensor circuit (Templifier).

3. Faulty control module.

4. Defective SA solenoid coil.

5. Faulty 4-way valve.

6. SA needle valve closed/restricted.

7. Vane damage

8. Wrong module jumper connection.

1. Faulty relays R1 R2,  R5,  R7.

1. Check continuity.

2. Setting, dashpot o i l level.

3a. Check resistor setting a

b. Check module setting

4. Secondary output

5. Fuses

1 Vane operation.

2. Measure pulse rate.

3. Observe suction pressure

4. Evaporator pressure drop

5. Superheat, subcooling

6. Measure temperature.

1 a. Check + 20 & + 6.2 VD

b. Check load action

2. Remove one sensor lead

3. Jumper COM & ISA.

4. Verify connections.

5. Solenoid action

6. Measure at 1WHT  & 3B

7. Open wide.

8. Check relay

9. Superheat.

IO. Mechanical action.

Il. Check switch junction.

1. 6.2  & ISA

2. Remove one sensor lead.

3a. Check + 20 & + 6.2 VD

b. Check load action

4. Check solenoid action.

5. Valve operation.

6. Open wide.

7. Mechanical action

8  Verify connections

1. To check relays, energizt

power and on/off switch t
Install each relay in R7 b
FAIL light should glow. P
RESET button. EXT FAIL
should go out and stay o
relay is faulty.

1. Contact McQuay Service.

2. Reset, add dashpot oil.

3a. Reset.

b. Recalibrate control module.

4. Replace.

5. Correct fault.

1. Reset vane speed needle valve

2. Adjust to slower rate.

3. Repair, replace.

4. Correct flow deficiency.

5. Adjust refrigerant charge

6. Adjust tower controls.

la. Replace module.

b. Replace module.

2. If compressor loads, replace

sensor.

3. If compressor loads, replace

sensor.

4. Correct pin connections.

5. Replace.

6. Reset or replace

7. Clean and reset.

8. Replace

9. Adjust charge.

10. Call McQuay Service.

11. Replace.

1.

 If compressor unloads, replace

sensor.

2. If compressor unloads, replace

sensor.

3a. Replace module.

b. Replace module.

4. Replace

5. Repair, replace.

6. Clean, reset.

7. Call McQuay Service.

8. Correct pin connections.

1. Replace faulty relay.

Page 22 / IM 307

Содержание PEH050

Страница 1: ...SINGLE COMPRESSOR CENTRIFUGAL CHILLERS PEH PHH 050 063 079 087 100 126 13600 Industrial Park Blvd P O Box 1551 Minneapolis MN 55440...

Страница 2: ...L E S H O O T I N G G U I D E 20 22 McQUAY CENTRIFUGAL OPERATING LOG 23 M c Q U A Y S E R V I C E P R O G R A M S 24 17 18 18 18 18 18 18 19 19 INTRODUCTION GENERAL DESCRIPTION The McQuay Model PEH Ce...

Страница 3: ...l startup of the chiller he will be available to answer any ques tions and to instruct in proper operating procedures It is recommended that the operator maintain an operating log for each individual...

Страница 4: ...erating circuit When this switch is turned on its self contained light will energize and the control circuit is ready for automatic operation of the compressor The Load Recycling Thermostat LRT sensin...

Страница 5: ...ion after Box time delay 1lO F Auto Temp Oil Assures minimum compressor casting temperature at startup Section Temp CE126 compressor only Liquid Injection Solenoid LIS None None Refrig Piping None Ope...

Страница 6: ...T 104 F Auto Control Box None On units with refrigerant cooled oil cooler controls oil sump heater to maintain set temperature Sequence Relay SR None None Field Suoolied None Relay controlled by syste...

Страница 7: ...eveloped by McQuay Guardistor Motor Protection Positive protection against motor overheating is provided by the Guardistor system The heart of the Guardistor protective circuit are the thermistors emb...

Страница 8: ...FF Switch with light 26 Gauges 1 Operating Relays R1 R10 2 Surgegard Relay 3 Guardistor Relay 4 Oil Pump Time Delay Switch 5 Anti Recycle Time Delay Relay 6 Prelube Timer 7 Oil Pump Safety Timer 8 Sys...

Страница 9: ...e module will function as follows Red will light during unloading control action green will light during loading and amber will light when the load action is overridden by the current limit control Re...

Страница 10: ...held in that position Refer to Figure 7 for solenoid action Note that both solenoids cannot be energized simultaneously METERING VALVES The speed at which the capacity control vanes are opened or clos...

Страница 11: ...l pump for the CEO50 compressor is completely self contained within the compressor housing The assembly in cludes the pump pump motor oil heater and oil separator The oil is pumped through the oil dis...

Страница 12: ...erant flow and keeps the machine from short cycling under light load con ditions It also prevents surge during heat recovery operation OPERATING THE CHILLER The initial startup of the McQuay centrifug...

Страница 13: ...temperature Normally the compressor will load to full load according to the settings of the control module ramp up control OPERATING CHECKS 1 While operating under automatic control the operator shoul...

Страница 14: ...compressor cannot be restarted unless the switch is repositioned If the operator has the need to secure the chiller and pro hibit starting by unauthorized personnel removal of relay R7 from its plug i...

Страница 15: ...ation of the expansion valves Proper superheat set ting is 2 to 6 F at full load ELECTRICAL SYSTEM Maintenance of the electrical system involves the general re quirement of keeping contacts clean and...

Страница 16: ...ush out condenser and check for leaks Refer to the procedures of Preliminary Checks Before Starting before energizing the compressor circuit REPAIR OF SYSTEM PUMPING DOWN If it becomes necessary to pu...

Страница 17: ...prevent localized freezing Consult the chiller nameplate for the proper refrigerant charge With a near normal charge in the system final charging can best be accomplished with the unit running with th...

Страница 18: ...the actual chilled water temperature This signal is calibrated at the factory or by the McQuay Service technician performing the initial startup of the chiller This signal normally is adjusted to appr...

Страница 19: ...ential Since the LRT scale is not highly accurate a practical set ting can be made with the machine running Turn the dial clockwise to a higher temperature until the compressor stops At this point com...

Страница 20: ...cts 3 Oil pump 4 Relay action 5 Relay action 6 Valve positron 7 Oil pressure drop 8 Feed oil lines for temperature 9a Pump b Relief valve c Filter d Bearings and seals 10 Opening closing pressure 1 Ch...

Страница 21: ...OAD RECYCLE 1 Normal shutdown 2 Load recycle thermostat 3 Anti recycle thermostat 1 Chilled water temperature satisfied 2a Setting drift b Loss of bulb charge 3a Time delay not yet timed o 4 Low sourc...

Страница 22: ...rate 3 Observe suction pressure 4 Evaporator pressure drop 5 Superheat subcooling 6 Measure temperature 1 a Check 20 6 2 VD b Check load action 2 Remove one sensor lead 3 Jumper COM ISA 4 Verify conn...