background image

2.

3.

4.

5.

6.

7.

FORCED CIRCULATION OF ANTIFREEZE THROUGH

THE WATER CIRCUITS IS THE ONLY SURE METHOD
OF AVOIDING TROUBLE.

Take measures to prevent the shutoff valve in the water
supply line from being accidentally turned on.

If a cooling tower is used and if the water pump will be

exposed to freezing temperatures, be sure to remove the
pump drain plug and leave it out so that any water which
may accumulate will drain away.

Open compressor disconnect switch, and remove
Fusetrons. If transformer is used for control voltage, the
disconnect must remain on to provide power to oil heater.
Set compressor switch to OFF position. To insure against
the possibility of an accidental start, remove relay R7 in
each control panel.

Check for corrosion and clean and paint rusted surfaces.

Clean and flush water tower for all units operating on a
water tower. Make sure tower “blowdown” or  bleedoff is
operating. Set up and use a good maintenance program
to prevent “liming up” of both tower and condenser. It
should be recognized that atmospheric air contains many
contaminants which increase the need for proper water
treatment. The use of untreated water may result in cor-
rosion, erosion, sliming, scaling or algae formation. It is
recommended the service of a reliable water treatment is
required-McQuay  assumes no responsibility for the
results of untreated or improperly treated water.

Remove condenser heads at least once a year and clean

condenser tubes.

ANNUALSTARTUP
A dangerous condition can exist if power is applied to a faul-
ty compressor motor starter which has been burned out. This
condition can exist without the knowledge of the person start-
ing the equipment.

This is a good time to check all the motor winding

resistance to ground. Annual checking and recording of this
resistance will provide a record of any deterioration of the
winding insulation. All new units have well over 100 megohms
resistance between any motor terminal and ground.

Whenever great discrepancies in readings occur or uniform

readings of less than 5 megohms are obtained, the motor
cover should be removed for inspection of the winding prior
to starting the unit. Uniform readings of less than 5 megohms
indicate motor failure is imminent and motor should be re-
placed or repaired. Repair before failure occurs can save a
great deal of time and labor expended in  the cleanup of a
system after motor burnout.

1.

2.

3.

4.

5.

6.

The control circuit should be energized at all times. If the
control circuit has been off and oil is cool, energize oil
heaters and allow 24 hours for heater to remove refrigerant
from the oil before starting.

Check and tighten all electrical connections.

Replace the drain plug in cooling tower pump if it was
removed at shutdown time the previous season.

Install Fusetrons in main disconnect switch (if removed).

Reconnect water lines and turn on supply water. Flush out
condenser and check for leaks.

Refer to the procedures of “Preliminary Checks Before
Starting” before energizing the compressor circuit.

REPAIR OF SYSTEM

PUMPING DOWN
If it becomes necessary to pump the system down, extreme

care should be used to avoid damage to the water chiller due
to freezing. Always make sure that full water flow is main-
tained through the chiller while pumping down. To pump

system down, close all liquid line valves. With all liquid line
valves closed and water flowing through chiller, start the com-
pressor. In order to pump system down as far as possible,
it will be necessary to bypass the low pressure override switch
and jumper the low pressure cutout. Set temperature module
to manual load position. Vanes must be open while pump-
ing down to avoid a surge or other damaging condition.

Operate machine until the suction pressure stabilizes at

approximately 20 to 25 psig.

Stop the machine. Allow pressure to buildup. Repeat this

procedure 3 times.

After the system has been pumped down, the gas pressure

remaining will have to be purged before the machine can be
serviced.

PRESSURE TESTING
No pressure testing is necessary unless some damage was
incurred. After repairs are made, pressure test the system
at a pressure that does not exceed the standby pressure in

the condenser. (A test pressure higher than condenser

pressure would open the discharge check valve and allow

flow of test pressure into condenser). In cases where the en-
tire refrigerant charge is lost, refer to the following para-

graphs. The evacuation procedure can be followed in both
cases.

Page 16 I IM 307

LEAK TESTING
In case of the loss of the entire refrigerant charge, the unit
should be checked for leaks prior to charging the complete
system. This can be done by charging only enough refrigerant
into the system to build the pressure up to approximately 10
psig and adding sufficient dry nitrogen to bring the pressure
up to a maximum of 125 psig and then leak test with Halide
or electronic leak detector. CAUTION: DO NOT USE OXY-
GEN TO BUILD UP PRESSURE AS A SERIOUS EXPLO-
SION CAN RESULT. A pressure regulating valve should
always be used on the drum being used to build the system
pressure. Also, do not exceed the test pressure given above.
When the test pressure is reached disconnect the gas
cylinder.

If any leaks are found in welded or silver soldered joints

or if it is necessary to replace a gasket, relieve the test
pressure in the system before proceeding. For copper joints,
silver solder is recommended.

After making any necessary repair, the system should be

evacuated as described below.

EVACUATION
After it has been determined that there are no refrigerant
leaks, the system should be evacuated using a vacuum pump
with a capacity of approximately 3 cu.  ft/min. and that will
reduce the vacuum to at least 1 millimeter (1000 microns).

A mercury manometer, electronic or other type of micron

 

gauge should be connected at the farthest point from the
vacuum pump. For readings below 1 millimeter, the electronic

or other micron gauge should be used.

Содержание PEH050

Страница 1: ...SINGLE COMPRESSOR CENTRIFUGAL CHILLERS PEH PHH 050 063 079 087 100 126 13600 Industrial Park Blvd P O Box 1551 Minneapolis MN 55440...

Страница 2: ...L E S H O O T I N G G U I D E 20 22 McQUAY CENTRIFUGAL OPERATING LOG 23 M c Q U A Y S E R V I C E P R O G R A M S 24 17 18 18 18 18 18 18 19 19 INTRODUCTION GENERAL DESCRIPTION The McQuay Model PEH Ce...

Страница 3: ...l startup of the chiller he will be available to answer any ques tions and to instruct in proper operating procedures It is recommended that the operator maintain an operating log for each individual...

Страница 4: ...erating circuit When this switch is turned on its self contained light will energize and the control circuit is ready for automatic operation of the compressor The Load Recycling Thermostat LRT sensin...

Страница 5: ...ion after Box time delay 1lO F Auto Temp Oil Assures minimum compressor casting temperature at startup Section Temp CE126 compressor only Liquid Injection Solenoid LIS None None Refrig Piping None Ope...

Страница 6: ...T 104 F Auto Control Box None On units with refrigerant cooled oil cooler controls oil sump heater to maintain set temperature Sequence Relay SR None None Field Suoolied None Relay controlled by syste...

Страница 7: ...eveloped by McQuay Guardistor Motor Protection Positive protection against motor overheating is provided by the Guardistor system The heart of the Guardistor protective circuit are the thermistors emb...

Страница 8: ...FF Switch with light 26 Gauges 1 Operating Relays R1 R10 2 Surgegard Relay 3 Guardistor Relay 4 Oil Pump Time Delay Switch 5 Anti Recycle Time Delay Relay 6 Prelube Timer 7 Oil Pump Safety Timer 8 Sys...

Страница 9: ...e module will function as follows Red will light during unloading control action green will light during loading and amber will light when the load action is overridden by the current limit control Re...

Страница 10: ...held in that position Refer to Figure 7 for solenoid action Note that both solenoids cannot be energized simultaneously METERING VALVES The speed at which the capacity control vanes are opened or clos...

Страница 11: ...l pump for the CEO50 compressor is completely self contained within the compressor housing The assembly in cludes the pump pump motor oil heater and oil separator The oil is pumped through the oil dis...

Страница 12: ...erant flow and keeps the machine from short cycling under light load con ditions It also prevents surge during heat recovery operation OPERATING THE CHILLER The initial startup of the McQuay centrifug...

Страница 13: ...temperature Normally the compressor will load to full load according to the settings of the control module ramp up control OPERATING CHECKS 1 While operating under automatic control the operator shoul...

Страница 14: ...compressor cannot be restarted unless the switch is repositioned If the operator has the need to secure the chiller and pro hibit starting by unauthorized personnel removal of relay R7 from its plug i...

Страница 15: ...ation of the expansion valves Proper superheat set ting is 2 to 6 F at full load ELECTRICAL SYSTEM Maintenance of the electrical system involves the general re quirement of keeping contacts clean and...

Страница 16: ...ush out condenser and check for leaks Refer to the procedures of Preliminary Checks Before Starting before energizing the compressor circuit REPAIR OF SYSTEM PUMPING DOWN If it becomes necessary to pu...

Страница 17: ...prevent localized freezing Consult the chiller nameplate for the proper refrigerant charge With a near normal charge in the system final charging can best be accomplished with the unit running with th...

Страница 18: ...the actual chilled water temperature This signal is calibrated at the factory or by the McQuay Service technician performing the initial startup of the chiller This signal normally is adjusted to appr...

Страница 19: ...ential Since the LRT scale is not highly accurate a practical set ting can be made with the machine running Turn the dial clockwise to a higher temperature until the compressor stops At this point com...

Страница 20: ...cts 3 Oil pump 4 Relay action 5 Relay action 6 Valve positron 7 Oil pressure drop 8 Feed oil lines for temperature 9a Pump b Relief valve c Filter d Bearings and seals 10 Opening closing pressure 1 Ch...

Страница 21: ...OAD RECYCLE 1 Normal shutdown 2 Load recycle thermostat 3 Anti recycle thermostat 1 Chilled water temperature satisfied 2a Setting drift b Loss of bulb charge 3a Time delay not yet timed o 4 Low sourc...

Страница 22: ...rate 3 Observe suction pressure 4 Evaporator pressure drop 5 Superheat subcooling 6 Measure temperature 1 a Check 20 6 2 VD b Check load action 2 Remove one sensor lead 3 Jumper COM ISA 4 Verify conn...

Страница 23: ...DESIGN CONDITIONS LOG SHEET JOB NO CHILLER NO Compressor F L A Condenser Pump F L A Chiller Pump F L A CHILLER GPM PRESS DROP LVG TEMP ENT TEMP REFRIG TEMP CONDENSER GPM PRESS DROP LVG TEMP ENT TEMP R...

Страница 24: ...y of maintenance services through its Nationwide Service Organization and can tailor these services to suit the needs of the building owner Most popular among these services is the McQuay Com prehensi...

Отзывы: