28
MWM-J_(ii)
Performance Data
(b) Indoor Condition:
25°C DB
,
16°C WB
Outdoor Condition:
40°C DB
Indoor DB
˚
C
Indoor WB
˚
C
Outdoor DB,
˚
C
40
TC (kW)
SHC (kW)
PI (kW)
16
24
10.42
10.23
4.36
25
...........................................
x
2
y
2
z
2
27
10.66
10.66
4.38
Total capacity, TC
Interpolation Method:
25º C – 24º C
=
x
2
– 10.42kW
27º C – 24º C
11.66kW – 10.42kW
x
1
= 10.50kW
Sensible capacity, SHC
Interpolation Method:
25º C – 24º C
=
y
2
– 10.23kW
27º C – 24º C
10.66kW – 10.23kW
y
2
= 10.37kW
Power Input, PI
Interpolation Method:
25º C – 24º C
=
z
2
– 4.36kW
27º C – 24º C
4.38kW – 4.36kW
z
2
= 4.37kW
Details:
1
st
Step:
To obtain the Total capacity, Sensible capacity and Power input for
(a) Indoor Condition:
25°C DB
,
16°C WB
Outdoor Condition:
35°C DB
Indoor DB
˚
C
Indoor WB
˚
C
Outdoor DB,
˚
C
35
TC (kW)
SHC (kW)
PI (kW)
16
24
10.85
10.39
4.00
25
...........................................
x
1
y
1
z
1
27
11.03
11.03
4.01
Total capacity, TC
Interpolation Method:
25º C – 24º C
=
x
1
– 10.85kW
27º C – 24º C
11.03kW – 10.85kW
x
1
= 10.91kW
Sensible capacity, SHC
Interpolation Method:
25º C – 24º C
=
y
1
– 10.39kW
27º C – 24º C
11.03kW – 10.39kW
y
1
= 10.60kW
Power Input, PI
Interpolation Method:
25º C – 24º C
=
z
1
– 4.00kW
27º C – 24º C
4.01kW – 4.00kW
z
1
= 4.00kW
Содержание M5WM10J
Страница 10: ...8 MWM J_ ii Application Information Model MWM20JR MLC20CR Model MWM15JR MLC15CR 70034 095236...
Страница 11: ...9 Application Information MWM J_ ii Model M5WM20J M5LC20CJ Model M5WM25J M5LC25CJ...
Страница 13: ...11 Application Information MWM J_ ii Model M5WM25JR M5LC25CRJ CHECK JOINT COOLING HEATING CAP TUBE...
Страница 60: ...58 MWM J_ ii Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model MWM20 25J Model MLC20 25C 70034 108883...
Страница 62: ...60 MWM J_ ii Wiring Diagram 70034 108882 Heat Pump Indoor Unit Outdoor Unit Model MWM20 25JR Model MLC20 25CR...
Страница 88: ......