68
MWM-J_(ii)
Troubleshooting
Diagnostic Guidelines
By means of pressure readings:
Data
Circuit
Pressure
Probable cause
Too low
A
little low
Normal
A
little high
Too high
High side
Low side
•
•
1. Overcharged with refrigerant.
2. Non-condensable gases in refrigerant circuit (e.g. air).
3. Obstructed air-intake / discharge.
4. Hot air short circuiting in outdoor unit.
High side
Low side
•
•
1. Poor compression /no compression (compressor
defective)
2. Reversing valve leaking.
High side
Low side
•
•
1. Undercharged with refrigerant.
2. Refrigerant leakage.
3. Air
fi
lter clogged / dirty (indoor unit).
4. Indoor fan locked / seized.
5. Defective defrost control, outdoor coil freeze up
(heating).
6. Outdoor fan locked / seized (heating).
High side
Low side
•
•
1. Outdoor fan blocked (cooling).
2. Outdoor coil dirty (cooling).
3. Indoor fan locked / seized (heating).
4. Indoor air
fi
lter clogged / dirty (heating).
5. Non-condensable gases in refrigerant circuit (e.g. air).
High side
Low side
•
•
1. Air intake temperature of indoor unit too high.
Содержание M5WM10J
Страница 10: ...8 MWM J_ ii Application Information Model MWM20JR MLC20CR Model MWM15JR MLC15CR 70034 095236...
Страница 11: ...9 Application Information MWM J_ ii Model M5WM20J M5LC20CJ Model M5WM25J M5LC25CJ...
Страница 13: ...11 Application Information MWM J_ ii Model M5WM25JR M5LC25CRJ CHECK JOINT COOLING HEATING CAP TUBE...
Страница 60: ...58 MWM J_ ii Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model MWM20 25J Model MLC20 25C 70034 108883...
Страница 62: ...60 MWM J_ ii Wiring Diagram 70034 108882 Heat Pump Indoor Unit Outdoor Unit Model MWM20 25JR Model MLC20 25CR...
Страница 88: ......