Application Information
MWM-J_(ii)
Vacuuming and Charging
The pre-charged outdoor unit does not need any vacuuming or charging. However once it is connected, the
connecting pipe line and the indoor unit need to be vacuumed before releasing the R22/R407C/R410A from
the outdoor unit.
1. Open the service port core cap.
2. Connect pressure gauge to the service port.
3. Connect the line to vacuum pump. Open the charging manifold valve and turn the pump on. Vacuum to -0.1
MPa (-760mmHg) or lower. (Evacuation time varies by the pump but averagely in 1 hour).
Filter Dryer
(Mclecular-Sieve Type
Note : R22 - Nil
R410A - Nil
4. After evacuation, unscrew the spindle (diagram B) for the gas to run to indoor unit.
Additional Charge
• The refrigerant gas is charged in the outdoor unit and, if the piping length is 7.6m, additional charge of the
refrigerant after vacuuming is not necessary.
• When the piping length is more than 7.6m, additional refrigerant charge (g) per additional 1m length as
tabulated:
R22
Indoor
MWM09/15J
MWM09/15JR
MWM20J
MWM20JR
MWM25J
MWM25JR
Outdoor
MLC09/15C
MLC09/15CR
MLC20C
MLC20CR
MLC25C
MLC25CR
Additional Charge (g/m)
16
23
15
22
39
55
R410A
Indoor
M5WM10/15J
M5WM10/15JR
M5WM20/25J
M5WM20/25JR
Outdoor
M5LC10/15C
M5LC10/15CR
M5LC20/25C
M5LC20/25CR
Additional Charge [g/m]
9
16
11
16
Содержание M5WM10J
Страница 10: ...8 MWM J_ ii Application Information Model MWM20JR MLC20CR Model MWM15JR MLC15CR 70034 095236...
Страница 11: ...9 Application Information MWM J_ ii Model M5WM20J M5LC20CJ Model M5WM25J M5LC25CJ...
Страница 13: ...11 Application Information MWM J_ ii Model M5WM25JR M5LC25CRJ CHECK JOINT COOLING HEATING CAP TUBE...
Страница 60: ...58 MWM J_ ii Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model MWM20 25J Model MLC20 25C 70034 108883...
Страница 62: ...60 MWM J_ ii Wiring Diagram 70034 108882 Heat Pump Indoor Unit Outdoor Unit Model MWM20 25JR Model MLC20 25CR...
Страница 88: ......