16
MWM-J_(ii)
Application Information
Piping Works
• Do not use contaminated or damaged copper tubing. Do not remove plastic, rubber plugs and brass nuts
from the valves,
fi
ttings, tubings and coils until you are ready to connect suction or liquid line into valves or
fi
ttings.
• If any brazing work is required, ensure that the nitrogen gas is passed through coil and joints while the
brazing work is being done. This will eliminate soot formation on the inside walls of the copper tubings.
• Cut the connection pipe with a pipe cutter.
Cutting copper tube
1/4t
• Remove burrs from cut edges of the pipes with remover. Hold the end of the pipe downwards to prevent
metal chips from entering the pipe.
Remove burr
• Insert the
fl
are nuts, mounted on the connection parts of both the indoor unit and outdoor unit onto the
copper pipes.
• Flare the pipe with extra length above the
fl
aring tool as shown in the table.
• The
fl
ared edge must be even and not cracked or scratched.
Ø Tube,
D (mm / in)
A (mm)
Imperial Die
Rigid Die
6.35 / 1/4
1.3
0.7
9.52 / 3/8
1.6
1.0
12.70 / 1/2
1.9
1.3
15.88 / 5/8
2.2
1.7
19.05 / 3/4
2.5
2.0
Swaging block
Copper tube
Piping Connection to the Units
• Align the center of the piping and tighten the
fl
are nut suf
fi
ciently with
fi
ngers.
• Finally tighten the
fl
are nut with torque wrench unit the wrench clicks.
• When tightening the
fl
are nut with torque wrench, ensure the direction for tightening follows the arrow on
the wrench.
Pipe Size (mm/in)
Torque (Nm)
6.35 (1/4)
18
9.52 (3/8)
42
12.70 (1/2)
55
15.88 (5/8)
65
19.05 (3/4)
78
Indoor piping
Flare nut
Flared tube
Flare joint
Spanar
Torque wrench
Содержание M5WM10J
Страница 10: ...8 MWM J_ ii Application Information Model MWM20JR MLC20CR Model MWM15JR MLC15CR 70034 095236...
Страница 11: ...9 Application Information MWM J_ ii Model M5WM20J M5LC20CJ Model M5WM25J M5LC25CJ...
Страница 13: ...11 Application Information MWM J_ ii Model M5WM25JR M5LC25CRJ CHECK JOINT COOLING HEATING CAP TUBE...
Страница 60: ...58 MWM J_ ii Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model MWM20 25J Model MLC20 25C 70034 108883...
Страница 62: ...60 MWM J_ ii Wiring Diagram 70034 108882 Heat Pump Indoor Unit Outdoor Unit Model MWM20 25JR Model MLC20 25CR...
Страница 88: ......