Troubleshooting
LED Indoor Lights: Normal Operation and Fault Conditions for Cooling / Heat Pump Unit
1
COOL/HEAT
(GREEN/RED)
Error
Code
Normal Operation / Fault Indi-
cation
Action
Green
-
Cool mode
-
Red
-
Heat mode
-
Red
-
Auto mode in Heating operation
-
Green
-
Auto mode in Cooling operation
-
-
Time on
-
-
Sleep mode on
-
-
Fan mode on
-
-
Dry mode on
-
1 time
Blink E1
Room air sensor contact loose
/ short
Check room sensor connection /
change room air sensor
3 times
Blink E3 Outdoor coil sensor open
Check outdoor coil sensor
connection / change outdoor coil
sensor
2 times
Blink E2 Indoor coil sensor open
Check indoor coil sensor
connection / change indoor coil
sensor
1 time
Blink E4
Compressor overload / indoor
coil sensor short /
outdoor coil sensor short
If running ampere highly increase,
change the compressor. If not,
replace the coil sensor.
Red
-
Defrost operation
-
3 times
Blink E5 Gas leak
Top up refrigerant / check for
leakage
6 times
Blink E8
Hardware error (tact switch pin
short)
Contact your distributor
4 times
Blink E9 No feedback from indoor fan
Contact your distributor
5 times
Blink
EE
EEPROM defrost
Contact your distributor
ON
ON or OFF
Blinking
Note: The unit will not detect sensor missing when the compressor is ON.
Содержание M5WM10J
Страница 10: ...8 MWM J_ ii Application Information Model MWM20JR MLC20CR Model MWM15JR MLC15CR 70034 095236...
Страница 11: ...9 Application Information MWM J_ ii Model M5WM20J M5LC20CJ Model M5WM25J M5LC25CJ...
Страница 13: ...11 Application Information MWM J_ ii Model M5WM25JR M5LC25CRJ CHECK JOINT COOLING HEATING CAP TUBE...
Страница 60: ...58 MWM J_ ii Wiring Diagram Cooling Only Indoor Unit Outdoor Unit Model MWM20 25J Model MLC20 25C 70034 108883...
Страница 62: ...60 MWM J_ ii Wiring Diagram 70034 108882 Heat Pump Indoor Unit Outdoor Unit Model MWM20 25JR Model MLC20 25CR...
Страница 88: ......