McQuay IM 685 Скачать руководство пользователя страница 23

IM 685 / Page 23

2.

Low CO

2

 Readings –

 Low CO

2

 readings that cannot be corrected can be caused by air leaking into

the heat exchanger and diluting the flue gas. If this is suspected, take two consecutive CO

readings,

one with the supply fan running and one with the supply fan off. If the CO

2

 increases with the

supply fan off, it could indicate leakage. Note that CO

samples must be taken from inside a tube,

not just from inside the flue box.

Checking for Leaks

1. Open up the rear casing panel while the unit is shut off and visually inspect the heat exchanger.
2. Visually inspect the heat exchanger while the burner is operating, looking for light coming through

holes. The burner should only be operated for a few minutes with the supply fan off, and take
necessary safety precautions around the hot heat exchanger.

3. Perform consecutive CO

2

 tests with supply fan off and on. See Item 2 under “Leakage Symptoms.”

4.

Smoke Bomb Test –

 Cover the flue box openings, open the rear casing panel so the heat exchanger

is accessible, toss a smoke bomb into the heat exchanger through the rear inspection port, replace the
port cover, and with a bright light look for smoke leaking through the heat exchanger. Remove the
remains of the smoke bomb and uncover the flue box openings before attempting to operate the
furnace.

Note:

 In most cases small leaks in the heat exchanger are not a source of danger. Because the pressure

created by the supply fan is greater than that inside the heat exchanger, the leakage will be 

into

 the heat

exchanger, not 

out of

 the heat exchanger and into the airstream.

Causes of Failures

1.

Improper Application –

 The furnace rating plate specifies a “Minimum Airflow CFM.” The furnace

must not be operated when airflow is below this minimum cfm. If the furnace is being used on a
variable air volume system, the control system must be such that the furnace will not operate when
the supply fan cfm has fallen below this minimum specified cfm. The furnace rating plate also
specifies a “Maximum MBH Input” which must not be exceeded. See “Verify Input Rate.”

2.

Control Failure –

 The limit control does not function properly to shut off the burner when the heat

exchanger temperature becomes excessive. In most situations, a properly controlled unit will never
even require the limit control to shut off the unit. The limit control should be a backup control and
a problem attributed to a limit failure would generally indicate a control problem in addition to the
limit failure.

3.

Excessive Condensation –

 Applications which will produce condensation require an all stainless steel

heat exchanger that is resistant to the effects of this condensation and that will give long heat
exchanger life. The likelihood of condensation increases with:
a.  Colder supply air temperature across the secondary tubes, as on units taking in a lot of outdoor air

in colder weather.

b.  Lower heat flow through the secondary tubes, as on modulating burners when operating at

reduced input.

c. High airflow across the secondary tubes such as any application with a low temperature rise

furnace.

4.

Chemical Deterioration – 

Refrigerant leaks, some aerosol can propellants, fumes from dry cleaning

establishments, beauty shops, swimming pools, and others, often have detrimental effects on heat
exchangers when they get into the combustion air supply and thereby into the combustion. Even
fumes from nearby roof exhaust fans can cause problems.

5.

Inadequate or Distorted Airflow –

 Internal baffles that have been repositioned or have loosened up

and moved can distort the airflow and cause failures. Construction rubbish, shipping cartons, and
insulation that has come loose will occasionally end up inside a unit and block airflow to part of the
furnace, resulting in a failure. These items can also alter the air or heat flow to the fan limit or some
other control and contribute to a failure.

Replacing Heat Exchanger

1. Remove the complete flue box, the casing panel through which the flue tubes pass, and the rear

inspection cover. Open the hinged rear door.

2. The burner is mounted on and supported by the heat exchanger studs with four nuts. When

removing the heat exchanger, the burner must either be removed or blocked in place. Remove the
four burner mounting nuts and the two exchanger bolts located 2" above the upper burner mounting
nuts.

Содержание IM 685

Страница 1: ...Gas Fired Furnace on McQuay Applied Rooftop Systems HT A with RM7895A Flame Safeguard Installation Maintenance Manual IM 685 Group Applied Systems Part Number 629948Y 00 Date March 1998 1998 McQuay I...

Страница 2: ...nty failure state the date of installation of the unit and the date of failure along with an explanation of the malfunctions and the description of the replacement parts required Parts are warranted f...

Страница 3: ...ssembly and requires no additional chimney flue pipe Breidert cap draft inducer etc Factory Mounting This burner and gas train has been installed and wired at the factory See Gas Piping Also note that...

Страница 4: ...the outside of the tube See Figure 1 Also apply a bead of high temperature silicone to seal both sides to the bottom of the flue box wrapper being careful not to obstruct the square drain holes in eac...

Страница 5: ...e burner is shown in Table 5 under Column 13 thru 15 Gas piping must be sized to provide the minimum required pressure at the burner when the burner is operating at maximum input Consult the appropria...

Страница 6: ...20 92 190 350 730 1100 2100 3300 5900 12000 30 73 152 285 590 890 1650 2700 4700 9700 40 63 130 245 500 760 1450 2300 4100 8300 50 56 115 215 440 670 1270 2000 3600 7400 60 50 105 195 400 610 1150 18...

Страница 7: ...s to avoid interference with swinging of doors etc Through the Curb Piping Models 020 thru 140 1 Remove bottom access panel See Figure 3c 2 Remove knockout and make an opening through bottom deck dire...

Страница 8: ...re only a connection to the supply gas line The manual shutoff valve is located within the burner vestibule If local codes require a manual shutoff valve that is accessible from outside the unit that...

Страница 9: ...tc 2 Review the equipment and service literature and become familiar with the location and purpose of the burner controls Determine where the gas and power can be turned off at the unit and upstream o...

Страница 10: ...electric gas valve in the line Open the gas line cocks upstream from there and bleed the gas line of all air Replace the 1 8 inch pipe plug 7 Leak check Using a rich soap water mixture and a brush ch...

Страница 11: ...until after a period of main flame operation has further purged the gas lines before trying to adjust out something that may actually be caused by air in the lines Modulate Firing Rates Set the tempe...

Страница 12: ...he flame safeguard FSG Upon a call for heat the control system will close OBA3 thus energizing relay R20 When 120 volt power is furnished through the system on off switch S1 through the burner on off...

Страница 13: ...flame rod FD at the completion of the 10 second trial for ignition period terminal 10 ignition transformer IT will be de energized and terminal 9 relay coil R23 and main gas valves GV4 etc will be ene...

Страница 14: ...history It can be mounted to the RM7895A and will retrieve information on the six most recent faults Consult the Honeywell bulletin 65 0090 1 7800 Series Keyboard Display Module and 65 0118 1 7800 Ser...

Страница 15: ...e RM7895A which are energized to indicate operation as follows POWER The RM7895A is powered PILOT The prepurge period is complete and the terminal for the start combination gas control is powered FLAM...

Страница 16: ...rly careful to correctly reinsert the air tube into the grommeted hole The tube should slip into the grommet so there is little leakage but it should not bear down on it or it can cause binding on the...

Страница 17: ...ure is not an option the following discussion on the High Pressure Regulator would still apply High Pressure Regulator If a high pressure regulator is included as part of the burner gas train or is in...

Страница 18: ...et that connects the air and gas valves must be correctly positioned on the control rod such that the bracket will be firmly held under tension against its stop when the actuator is in the minimum rat...

Страница 19: ...of 2000 feet and higher the gas burner must be derated 4 for every 1000 feet of altitude Example Model HT080 at an altitude of 3000 feet is derated 0 04 x 3 0 12 At 1000 mbh input 1000 x 0 12 120 mbh...

Страница 20: ...e adjusted to the flow rate used for this procedure is too high and must be reduced by repositioning the actuator to a lower firing rate or the gas supply line pressure is too low After adjusting valv...

Страница 21: ...will be diluted with outside air and lower readings will result If flue gas temperature is to be measured this must be done in the flue box not in the tube The temperature gradient within the tubes w...

Страница 22: ...bulator in each tube approximately flush with the tube end locking them in place with the wedge clips on each turbulator 8 Reinstall flue box front wrap Figure 14 Models 020 thru 025 Heat Exchanger Le...

Страница 23: ...Rate 2 Control Failure The limit control does not function properly to shut off the burner when the heat exchanger temperature becomes excessive In most situations a properly controlled unit will nev...

Страница 24: ...condensate However suitable steps should be taken to manage the flow of the condensate produced Most condensate will be produced in the secondary tubes where flue gas will sweep it into the flue box C...

Страница 25: ...eyboard display module or a DC voltmeter Twice Yearly 1 Burner Air Check burner fan wheel for dirt build up and lint Check combustion air intake louver and flue box for dirt buildup and accumulation o...

Страница 26: ...als 7 and L2 on the flame safeguard stays there the Keyboard when the burner fan is running Display Module indicates Purge Hold 2 2 Burner motor runs valve a Timer TD10 is not making after 20 seconds...

Страница 27: ...ressure will build up on the downstream side thus exceeding the rating of the gas train components b Undersized piping can also cause problems by delivering reduced pressure during times of maximum de...

Страница 28: ...64148A 04 040 Burner Gun Assembly 1 964148A 05 050 Burner Gun Assembly 1 964148A 06 064 065 Burner Gun Assembly 1 964148A 08 079 080 Burner Gun Assembly 1 964148A 10 100 Burner Gun Assembly 1 964148A...

Страница 29: ...N n i M M F C x a M R T F g e D g n i r u D e g r u p e r P e t a R x a M r e n r u B g n i t a r e p O e t a R x a M g n i r u D e g r u p e r P e t a R x a M x a M e t a R n i M e t a R 5 e t o N 5...

Страница 30: ...T t n e i b m A F g e D e r u t a r e p m e T s a G e u l F t n e c r e p 2 O C M P P O C C W n I x o B n i e r u s s e r P r i A Flue Gas Flue Gas s t n e m m o C y n a e z i r a m m u S k r o w e c...

Страница 31: ...IM 685 Page 31 Notes...

Страница 32: ...13600 Industrial Park Boulevard P O Box 1551 Minneapolis MN 55440 USA 612 553 5330...

Отзывы: