CONVERTER INSTALLATION
Copyright © 2018 McCrometer, Inc. All printed material should not be changed or altered without permission of McCrometer.
Any published technical data and instructions are subject to change without notice. Contact your McCrometer representative
for current technical data and instructions.
www.mccrometer.com
3255 WEST STETSON AVENUE • HEMET, CALIFORNIA 92545 USA
Printed In The U.S.A.
TEL: 951-652-6811 • 800-220-2279 • FAX: 951-652-3078
Lit. # 30122-46 Rev. 1.2 / 5-31-18
4
2.0
CONVERTER INSTALLATION
2.1
Mounting The Converter
If possible mount the converter in an electronics shed or environmental enclosure. If the converter is mounted
outdoors a sun shield is recommended. The sun shield should be oriented in a direction to reduce sun damage
and ensure readability. The converter is mounted using 2 bolts.
See Figure 1
. A service loop in the cables is
required.
See Section 3.2
. This electronic unit is rated IP67 for temporary flooding.
2.2
Installing Cables To Converter And Service Loop
Conduit of any kind
CANNOT
be attached directly to the electronics enclosure. Attaching conduit directly to the
enclosure will introduce dangerous gasses and moisture into the enclosure creating a dangerous condition, and
will remove the enclosure's IP67 rating.
Attaching conduit to the enclosure or altering the enclosure in any
way will void the warranty.
Any cable running through a conduit must exit the conduit and have a minimum of an 8" service loop before
entering the electronics enclosure through the cable glands. All cable compression glands must be properly
tightened to prevent moisture intrusion and maintain the IP67 rating. This allows the electronics enclosure to be
rotated and the rear panel to be accessed. If electrically bonding (grounding) the enclosure to metallic conduit
or raceways, secure a lead wire to the enclosures back panel screw and attach the lead to a listed and approved
conduit grounding bushing. See
Figure 3
. To insure IP67 rating use only round cable 0.125" to 0.375" in diameter.
Figure 3.
Cable Installation, A Service Loop And Bonding To Metallic Conduit
WARNING:
Do not connect any form of conduit directly to the converter enclosure. Doing so will allow
moisture and potentially dangerous gasses to enter directly into the converter. Attaching any conduit to
the enclosure, or altering the enclosure in any way will void the warranty.
!
Grounding Lead
Sensor Cables
(Showing 8”
Service Loop)
Power Cable
Conduit Grounding
Bushings
Enclosure Front
Enclosure Back
Enclosure
Backplate
Screw
IMPORTANT
: All cables must have a minimum 8" service loop.