COMMERCIAL MULTI LOAD DRYERS - MDG30, MC2, PC2, PNA, and MNA

Illus. C

 (refers to the 

previous page 5-5

) shows the minimum cross-section area for horizontal multiple dryer venting.

These figures 

must be

  increased in proportion if the main duct run from the last dryer to where the exhaust has

numerous elbows or is unusually long.

  IMPORTANT:

 For extended duct work runs, the cross-section area of the duct can only be increased to an

     extent. For extended duct work runs, a professional HVAC firm 

should be

 consulted for

     proper venting information.

VERTICAL VENTING

ILLUS. D

The maximum length of venting from the last dryer to where it exhausts...

Vertical venting 

must not

 exceed 2 feet - this calculation compensates for the sue of a maximum of three (3)

           elbows including the two (2) elbows creating the 180

°

 (turned down-

           ward outside outlet protection.

  IMPORTANT:

  

No more than

 four (4) dryers maximum 

should be

 connected to one (1) main common duct

      with a vertical run.

  NOTE:

  Distance between dryer single ducts being connected to the main common duct 

must be

 a minimum of

     31-3/8” (dryer width).

     Ducts work 

should be

 laid out in such a manner where allowances are made at rear area of the dryer for

     removal of rear service panels or guards.

Illus. D

 shows the minimum cross-section  area for vertical multiple dryer venting. These figures 

must be

 increased in

proportion if the main duct run from the last dryer to where it exhausts has numerous elbows or is unusually long.

  IMPORTANT:

  For extended duct work runs, the cross-section area of the duct can only be increased to an

      extent. For extended duct work runs, a professional HVAC firm 

should be

 consulted for

      proper venting information.

Содержание MDG30PCCWW

Страница 1: ...lbs 250 Kg Uncrated 500 lbs 227 Kg Gas Inlet 1 2 I D ELECTRICAL REQUIREMENTS 120 volts 60 Hz single phase some 240 volts 50 Hz models available for export Individual branch circuit serving only the dr...

Страница 2: ...ich it is connected ALL duct work joints must be taped to prevent moisture and lint from escaping into the building Additionally inspection doors should be installed at strategic points in the exhaust...

Страница 3: ...single 8 inch venting is used the duct work to the outlet cannot exceed 30 feet refer to Illus A below This calculation of 30 feet compensates or allows for the use of a maximum of only one 1 elbow RE...

Страница 4: ...ard outside outlet Illus B VERTICAL SINGLE DRYER VENTING NOTE A OPENING MUST BE TWO 2 INCHES LARGER THAN THE DUCT ALL THE WAY AROUND THE DUCT MUST BE CENTERED WITHIN THIS OPENING If the length of the...

Страница 5: ...cted to one 1 main common duct run The main common duct may be any shapes so long as the minimum cross section area is provided The main duct should be tapered with the diameter in creasing before eac...

Страница 6: ...mum of three 3 elbows including the two 2 elbows creating the 180 turned down ward outside outlet protection IMPORTANT No more than four 4 dryers maximum should be connected to one 1 main common duct...

Страница 7: ...he duct work for periodic inspection and cleaning 9 Where ever the duct passes through combustible materials the opening must be 2 inches larger all the way around than the duct The duct must be cente...

Страница 8: ...air openings are acceptable IMPORTANT Makeup air must be provided from a source free of contaminating fumes such as dry cleaning fumes Make up air contaminated by dry cleaning solvent fumes will resu...

Отзывы: