background image

6-8

07/02

TYPICAL NATURAL GAS INSTALLATION

GAS SHUT-OFF VALVES

3/4 PIPE GAS LOOP

DRYERS

GAS WATER HEATERS

GAS SERVICE
LINE TAP

GAS METER

IN LINE PRESSURE
REGULATOR IF (NATURAL)
GAS LINE PRESSURE
EXCEEDS 12
WATER COLUMN PRESSURE

COMMERCIAL MULTI LOAD DRYERS - MDG30, MC2, PC2, PNA, and MNA

MAKE-UP AIR REQUIREMENTS

• Makeup area opening must have 1 square feet for each dryer.

• Common makeup air openings are acceptable.

IMPORTANT: 

Makeup air must be provided from a source free of contaminating fumes such as

dry cleaning fumes. Make-up air contaminated by dry cleaning solvent fumes will result in
irreparable damage to motors and other dryer components.

GAS REQUIREMENTS

• Gas inlet 1/2" (1.27 cm) NPT.

• Product comes equipped to use natural gas.

• Accessible line shutoff is recommended.

• Natural gas supply pressure must be 6-12" water column.

• Water column pressure requirements measured at the gas valve tap

- 4" Natural gas
- 11" LP gas

2'

2'

2'

2'

MAKE UP AIR OPENINGS

FOR 8 DRYERS

INCHES

Содержание MDG30PCCWW

Страница 1: ...lbs 250 Kg Uncrated 500 lbs 227 Kg Gas Inlet 1 2 I D ELECTRICAL REQUIREMENTS 120 volts 60 Hz single phase some 240 volts 50 Hz models available for export Individual branch circuit serving only the dr...

Страница 2: ...ich it is connected ALL duct work joints must be taped to prevent moisture and lint from escaping into the building Additionally inspection doors should be installed at strategic points in the exhaust...

Страница 3: ...single 8 inch venting is used the duct work to the outlet cannot exceed 30 feet refer to Illus A below This calculation of 30 feet compensates or allows for the use of a maximum of only one 1 elbow RE...

Страница 4: ...ard outside outlet Illus B VERTICAL SINGLE DRYER VENTING NOTE A OPENING MUST BE TWO 2 INCHES LARGER THAN THE DUCT ALL THE WAY AROUND THE DUCT MUST BE CENTERED WITHIN THIS OPENING If the length of the...

Страница 5: ...cted to one 1 main common duct run The main common duct may be any shapes so long as the minimum cross section area is provided The main duct should be tapered with the diameter in creasing before eac...

Страница 6: ...mum of three 3 elbows including the two 2 elbows creating the 180 turned down ward outside outlet protection IMPORTANT No more than four 4 dryers maximum should be connected to one 1 main common duct...

Страница 7: ...he duct work for periodic inspection and cleaning 9 Where ever the duct passes through combustible materials the opening must be 2 inches larger all the way around than the duct The duct must be cente...

Страница 8: ...air openings are acceptable IMPORTANT Makeup air must be provided from a source free of contaminating fumes such as dry cleaning fumes Make up air contaminated by dry cleaning solvent fumes will resu...

Отзывы: