background image

6-5

07/02

COMMERCIAL MULTI LOAD DRYERS - MDG30, MC2, PC2, PNA, and MNA

MULTIPLE DRYER (Common) VENTING

HORIZONTAL VENTING

If it is not feasible to provide separate exhaust ducts for each dryer, ducts for individual dryers may be channeled into
a common main duct. Each dryer is provided with a back draft damper. The individual ducts should enter the bottom or
side of the main duct at an angle not more than 45

°

 in the direction of the airflow. No more than four (4) dryers 

should

be

 connected to one (1) main common duct run.

The main common duct may be any shapes so long as the minimum cross-section area is provided. The main duct should
be tapered with the diameter in creasing before each individual 8-inch duct is added (refer to 

Illus. C and Illus D

).

Illus. C

Horizontal venting 

must not

 exceed 20 feet - this calculation compensates for the use of a maximum of only one

(1) elbow which is the outside outlet protection.

  

NOTE:

  Distance between dryer ducts being connected to the main common duct 

must be

 a minimum of

     31-1/8” (dryer width).

     Duct work 

should be

 laid out in such a manner where allowances are made at rear area of the dryer

     for removal of rear panels or guards.

Содержание MDG30PCCWW

Страница 1: ...lbs 250 Kg Uncrated 500 lbs 227 Kg Gas Inlet 1 2 I D ELECTRICAL REQUIREMENTS 120 volts 60 Hz single phase some 240 volts 50 Hz models available for export Individual branch circuit serving only the dr...

Страница 2: ...ich it is connected ALL duct work joints must be taped to prevent moisture and lint from escaping into the building Additionally inspection doors should be installed at strategic points in the exhaust...

Страница 3: ...single 8 inch venting is used the duct work to the outlet cannot exceed 30 feet refer to Illus A below This calculation of 30 feet compensates or allows for the use of a maximum of only one 1 elbow RE...

Страница 4: ...ard outside outlet Illus B VERTICAL SINGLE DRYER VENTING NOTE A OPENING MUST BE TWO 2 INCHES LARGER THAN THE DUCT ALL THE WAY AROUND THE DUCT MUST BE CENTERED WITHIN THIS OPENING If the length of the...

Страница 5: ...cted to one 1 main common duct run The main common duct may be any shapes so long as the minimum cross section area is provided The main duct should be tapered with the diameter in creasing before eac...

Страница 6: ...mum of three 3 elbows including the two 2 elbows creating the 180 turned down ward outside outlet protection IMPORTANT No more than four 4 dryers maximum should be connected to one 1 main common duct...

Страница 7: ...he duct work for periodic inspection and cleaning 9 Where ever the duct passes through combustible materials the opening must be 2 inches larger all the way around than the duct The duct must be cente...

Страница 8: ...air openings are acceptable IMPORTANT Makeup air must be provided from a source free of contaminating fumes such as dry cleaning fumes Make up air contaminated by dry cleaning solvent fumes will resu...

Отзывы: