121022 v1.02-RiA
Operating instructions SG-RS 309-2
Page 19/23
Maintenance and cleaning
Fault indication
Possible cause
Remedy
Green “P” LED not light-
ing up
No or incorrect supply voltage
1. Check supply voltage, compare with
type plate
2. Check terminal assignment
If supply voltage is correctly connect-
ed: control unit is faulty
Ä
Replace control unit
Yellow “S1” LED is lit up Sensor 1 is faulty
1. Measure resistance at sensor 1: target
value = 8k2 ±5% or 10k ±5%
2. Actual value ≠ target value: sensor is
faulty
3. Replace sensor
Control unit is faulty
1. Connect an 8k2 or 10k resistor to
terminals Y1, Y2
2. Fault not rectified: replace control unit
Yellow “S2” LED is lit up Sensor 2 is faulty
1. Measure resistance at sensor 2: target
value = 8k2 ±5% or 10k ±5%
2. Actual value ≠ target value: sensor is
faulty
3. Replace sensor
Control unit is faulty
1. Connect an 8k2 or 10k resistor to
terminals Y3, Y4
2. Fault not rectified: replace control unit
Cleaning
Ä
Clean the outside of the enclosure with a dry cloth.
Maintenance and cleaning
Maintenance
The control unit is maintenance-free.
Ä
Repeat the functional test monthly.
Prerequisites:
•
The sensor system has passed the latest test (see sensor installation instruc-
tions).
•
The control unit is connected to the supply voltage and sensor.
•
No sensor is activated.
Troubleshooting and remedies