121022 v1.02-RiA
Operating instructions SG-RS 309-2
Page 17/23
Commissioning
8. Repeat step 1.
9. Interrupt the power supply for at least 500 ms.
The control unit will restart.
10. Repeat step 2.
11. If connected, disconnect sensor 2.
-
Yellow “S2” LED and red “F” LED are flashing
-
OSSDs from monitoring circuits 1 and 2 are in the OFF state
-
Signal outputs M1 and M2 are set to HIGH
12. Repeat step 1.
13. Interrupt the power supply for at least 500 ms.
The control unit will restart.
14. Repeat step 2.
Throughout the entire time the protective device remains activated, the OSSDs
stay in the OFF state.
If the protective device stops being activated, various states are possible for the
OSSDs. This depends on which reset type is selected (see
Function
,
Reset
).
Protective device activated
Once the functional test has been successfully completed, the protective device is
ready for operation.
If the functional test could not be completed correctly, see
Troubleshooting and
remedies.