background image

Change LCK to 0101 then press 
the            key and           key for 
4 seconds to level 3

Operating display

Level3 (Input level)

Name

Description

Ex-

factory

Inp1

Main input selections

Select the input range, refer to input selection

K1

dP

Decimal point

Set the position of decimal point

000.0

LSPL

Lower set point limit

Set lower point within INP1

0.0

USPL

Upper set point limit

Set highest point within INP1

400

ALd1

Alarm mode of AL1

Range of setting; oo~19

11

ALt1

Alarm 1 time set

It is used in program function. Range: 
00~99.59mm, 0=flicker alarm, 99.59=continued 
alarm, others=on delay time

99.59

ALd2

Alarm mode of AL2

Range of setting: 00~19

11

ALt2

Alarm 2 time set

It is used in program function. Range: 
00~99.59mm, 0=flicker alarm. 99.59=continued 
alarm, others=on delay time.

99.59

ALd3

Alarm mode of AL3

Range of setting: 00~19

11

ALt3

Alarm 3 time set

It is used in program function Range 
00~99.59mm 0=flicker alarm 99.59=continued 
alarm, others=on delay time

99.59

HYSA

Hystersis of alarm

Range of setting: 0.4~100.0

0.4

CLO1

Output1 zero set

Calibrate the low value of output1

Range of setting: 0-2000( current output only )

400

CHO1

Output1 span set

Calibrate the high value of output1

Range of setting; 0-2000( current output only )

2000

OPrL

Transmitter zero set

Calibrate the low value of transmitter 

Range of setting; 0-2000

400

OPrH

Transmitter span set

Calibrate the high value of transmitter 

Range of setting; 0-2000

2000

rUCY

The time from open 

to close of motor

Full run time of proportional motor, Range of 
setting: 0~150Sec

5

WAit

Use in program for 

SV wait PV

0=No wait

Other=Wait Volume

0.0

idNO

ID number

Communication ID number

1

bAUd

Baud-rate

UART baud rate selection

Range of setting:110-38.4K BIT/sec

2.4k

SVOS

Compensate SV

Range of setting:-100.0~100.0

0.0

PVOS

Compensate PV

Range of setting:-100.0~100.0

0.0

Unit

Unit of PV 

SV

Range of setting: C,F,A (analog)

SOFt

Soft filter

Adjust the response time of PV, the little the 
faster Range of setting:0~254

200

CASC

Cluster control

(don’t care)

Range of setting:0~1000

0.0

TOH

The time for loop 

open

Range of setting:0~120 sec.

60

TsH

The time for loop 

short

Range of setting:0~120 sec.

20

Press the            key

Repeat the same 
steps as above to 
display the parameters

listed at right.

27.5

27.5

PV

SV

InP1

K1

PV

SV

SET

dP

000.0

PV

SV

SET

Press the            key

SET

LSPL

000.0

PV

SV

Press the            key

SET

USPL

400.0

PV

SV

Press the            key

SET

ALd1

000.0

PV

SV

Return to “

P.4

Содержание MC-2438

Страница 1: ...MC 2 SERIES OPERATION MANUAL MAXTHERMO MAXTHERMO GITTA GROUP CORP GITTA GROUP CORP Version Version 0711070001 0711070001...

Страница 2: ...cification Error information Error information Input selection table Input selection table Alarm selection table Alarm selection table P 1 P 2 P 3 P 7 P 11 P 11 P 12 P 17 Alarm action description Alar...

Страница 3: ...44 5 44 5 65 70 50 50 80 17 MC 2538 44 5 90 5 111 116 50 96 80 17 MC 2638 90 5 44 5 65 70 96 50 80 17 MC 2738 68 5 68 5 89 94 74 74 80 17 MC 2838 90 5 90 5 111 116 96 96 80 17 A C D B F E H G unit mm...

Страница 4: ...Output1 action indication 1 1 PV Process value display 9 9 OUT 2 Output2 action indication 10 10 AT Auto tuning action indication 2 2 SV Set value 11 11 AL 1 Alarm1 action indication 3 3 SET Set key e...

Страница 5: ...tuning off set Range of setting 0 100 F S 0 CYT1 Main Control Output cycle time When output is SSR it is set at 3 4 20 mA is set at 1 but output is relay usually it is set at 20 Range of setting 0 100...

Страница 6: ...utput only 400 CHO1 Output1 span set Calibrate the high value of output1 Range of setting 0 2000 current output only 2000 OPrL Transmitter zero set Calibrate the low value of transmitter Range of sett...

Страница 7: ...0 the parameter is skipped If the digit set at 1 the parameter is opened PrOG 0 Program no repeat 1 Program repeat 0 Without power failure 1 With power failure 0 Start from 0 1 Start from PV 0 Alarm...

Страница 8: ...of setting LSPL USPL tM 4 Set time for seg 4 Range of setting 0 99 hours 59 min OUT4 Set output for Seg 4 Range 0 100 SV 5 Set volume for seg 5 Range of setting LSPL USPL tM 5 Set time for seg 5 Rang...

Страница 9: ...OH time it is loop open 3 Program It doesn t need installing hardware but has to modify software as following steps a Open MODE in level 4 and set mode 3rd 4th digit to 01 then the parameter of proces...

Страница 10: ...ogram will perform again from stopped segment when the power is recovered On the contrary if the PROG 1st digit set 0 it hasn t power failure function the program always perform again from first segme...

Страница 11: ...to 01 in level4 to open motor valve control function d Set CYT1 to open close cycle time of motor valve in level2 and RUCY to time from open to close of motor valve in level3 e The LED bar on the pan...

Страница 12: ...2438 series don t have this function SET A M A M P 10 1 I 1 Input Main nput Main 1 T C Thermocouple S B R K E J W N Cu or PT100 selectable 2 DC V 10 10mV 0 10mV 0 20mV 0 50mV 0 1V 0 5V 0 10V selectab...

Страница 13: ...failed AutF Auto tuning failed NOTE If the marked error occurs the Temperature Controller need repair Please send it to the nearest sales office or retail dealer Error information Error information T...

Страница 14: ...13 Deviation high low limit alarm NO 04 14 Dand alarm NO 05 Absolute value high limit alarm YES 15 Absolute value high limit alarm NO 06 Absolute value low limit alarm YES 16 Absolute value low limit...

Страница 15: ...Option A Power Supply B Control Output C Input D Alarm F Communication Relay SSR mA V Relay SSR Proportional Motor Valve Control OUT1 Option CLOSE OPEN COM AL1 AL2 OUT1 OUT2 mA V RTD TC mV Use OUT1 O...

Страница 16: ...MC 2738 AC 85 265V DC 15 50V Option A Power Supply B Control Output C Input D Alarm E Retransmission F Remote G Communication Relay SSR mA V Relay SSR OUT1 OUT2 NO NC COM mA V RTD TC mV TRS NO COM NC...

Страница 17: ...538 MC 2638 AC 85 265V DC 15 50V Option A Power Supply B Control Output C Input D Alarm E Retransmission G Communication F Remote Relay SSR mA V Relay SSR OUT1 OUT2 OUT1 Option Proportional Motor Valv...

Страница 18: ...18 19 20 12 13 11 4 5 3 6 7 14 15 MC 2838 AC 85 265V DC 15 50V Option A Power Supply B Control Output C Input D Alarm G Communication F Remote OUT1 OUT2 Relay SSR mA V Relay SSR Proportional Motor Va...

Страница 19: ...HIGH OFF ON LOW HIGH OFF ON LOW HIGH OFF ON 06 Absolute low alarm inhibit 16 Absolute low alarm no inhibit 07 Segment end alarm use for Program Model only 1 ALD1 3 set 07 2 AL1 3 alarm segment No set...

Страница 20: ...phase SCR A 0 5V B 0 10V C 1 5V C C Out 2 control output mode for cooling Out 2 control output mode for cooling 0 None 1 Relay contact SPDT 5A 240VAC 2 SSR Voltage pulse 20VDC 20mA 3 Current 4 20mA A...

Страница 21: ...VE MC 2438 V V V V V V V MC 2538 V V V V V V V V MC 2638 V V V V V V V V MC 2738 V V V V V V V MC 2838 V V V V V V V V MC 2438 1 6 select 1 4 6 select 1 2 5 7 8 select 1 MC 2738 1 6 select 1 2 4 selec...

Отзывы: